Temposonics
®
R-Series
Brief Instructions
I
16
I
5.5 DeviceNet
D51
power supply
M12 male connector
(A-coded)
Pin
Function
1
2
3
4
5
View on sensor
1
Shield
2
+24 VDC (−15 / +20 %)
3
DC Ground (0 V)
4
CAN_H
5
CAN_L
DeviceNet LED status
Network status
Green
Red
Information
ON
OFF
Normal function
Flashing
OFF
Waiting for instructions from
DeviceNet master
OFF
ON
Initialization error
OFF
Flashing No answer from DeviceNet master
Modul status
Green
Red
Information
ON
OFF
Normal function
OFF
ON
Magnet not detected
5.6 EtherCAT
®
D56
Signal
M12 female connector
(D-coded)
Pin
Function
2
3
4
5
1
View on sensor
1
Tx (+)
2
Rx (+)
3
Tx (−)
4
Rx (−)
5
Not connected
M12 female connector
(D-coded)
Pin
Function
2
3
4
5
1
View on sensor
1
Tx (+)
2
Rx (+)
3
Tx (−)
4
Rx (−)
5
Not connected
Power supply
M8 male connector
Pin
Function
2
4
1
3
View on sensor
1
+24 VDC (−15 / +20 %)
2
Not connected
3
DC Ground (0 V)
4
Not connected
EtherCAT LED status
Green
Red
Information
Flashing
OFF
Normal function
Flashing
ON
No magnet / wrong quantity of magnets
Further diagnostic functions can be programmed.