8
Modbus Interface Manual
LP Series
Fault
Code
Description Corrective Action
101
Missing
Magnet
• Verify Float Configuration is correct for the
number of floats installed.
• Verify Float(s) are not in inactive zone.
• Verify Auto Threshold is enabled.
• Cycle power to sensor. If proper operation
is not restored, Contact Factory.
102
Internal
Fault 1
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
103
Internal
Fault 2
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
104
Internal
Fault 3
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
105
Lobe Fault 1 • Verify Auto Threshold is enabled
• Cycle power to sensor.
• If proper operation is not restored, Contact
Factory.
106
Lobe Fault 2 • Verify Auto Threshold is enabled.
• Cycle power to sensor.
• If proper operation is not restored,
Contact Factory.
107
Delta Fault
Contact Factory to discuss application.
108
Internal
Fault 4
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
109
Peak Fault
• Verify Auto Threshold is enabled.
• Cycle power to sensor.
• If proper operation is not restored,
Contact Factory.
110
Hardware
Fault 1
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
111
Power Fault
• Cycle power to sensor.
• Verify Power Supply rating.
• Verify wiring.
• If proper operation is not restored,
Contact Factory.
112
Hardware
Fault 2
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
113
Hardware
Fault 3
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
114
Hardware
Fault 4
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
115
Timing
Fault 1
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
116
Timing
Fault 2
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
117
Timing
Fault 3
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
118
DAC Fault 1
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
119
DAC Fault 2
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
8. Error Codes (Faults)
9. Modbus Interface
Note:
Termination and biasing of RS-485 data lines are as follows:
Biasing
Each LP-Series transmitter uses a Fail-Safe, Slew-Rate-Limited RS-
485/RS-422 Transceivers. No additional biasing, resistors should
be present on the connecting devices (PLC, DCS, PC, Converter).
Termination
Each LP-Series transmitter uses a Fail-Safe, Slew-Rate-Limited RS-
485/RS-422 Transceivers. No additional termination resistors are
necessary in connecting devices (PLC, DCS, PC, Converter).
Fault
Code
Description Corrective Action
120
DAC Fault 3
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
121
DAC Fault 4
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
122
SPI Fault 1
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
123
SPI Fault 2
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
124
Setpoint
Fault
The analog setpoints are too close. Mini-
mum distance is 150 mm (6 in.) for analog
and 290 mm (11.5 in.) for SIL. Adjust
programmed setpoints as needed. (Analog
only) If proper operation is not restored,
Contact Factory.
125
Loop 1 Out
of Range
Verify that magnets are positioned within
expected measuring range. Adjust program-
med setpoints as needed. (Analog only) If
proper operation is not restored, Contact
Factory.
126
Loop 2 Out
of Range
Verify that magnets are positioned within
expected measuring range. Adjust program-
med setpoints as needed. (Analog only) If
proper operation is not restored, Contact
Factory.
127
EEPROM
Fault 1
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
128
EEPROM
Fault 2
Cycle power to sensor. If proper operation
is not restored, Contact Factory.
129
Flash Failure Cycle power to sensor. If proper operation
is not restored, Contact Factory.
130
Internal
Error
Cycle power to sensor. If proper operation
is not restored, Contact Factory.