HAPTER
10
T
ROUBLE
SHOOTING
PROBLEM CAUSE SYMPTOM REMEDY
A
Water
temperature
higher than the
expected value.
A1
Thermal load too high.
A1.1
Water temperature higher
than expected value.
Restore the thermal load to
within the preset limits.
A2
Ambient temperature too high.
A2.1
See
A1.1
Restore the ambient
temperature to within the
preset limits.
A3
Condenser fins dirty.
A3.1
See
A1.1
Clean the condenser fins.
A4
Front surface of the condenser
obstructed.
A4.1
See
A1.1
Free the front surface of the
condenser.
A5
No refrigerant fluid in the plant.
A5.1
• See
A1.1
• low evaporation pressure.
Get a technician to
check for leaks and eliminate
them.
Fill the plant.
B
Probe (-BT1)
faulty
B1
Probe faulty or parameters out of range.
B1.1
Message P1 appears.
Check or renew the probe.
C
Low water
pressure at
pump outlet.
C1
Clearance between the impeller and the
pump casing too high. Wear parts.
C1.1
Low water pressure at pump
outlet.
Verify and replace the pump
impeller.
D
The
chille
r
is obstructed
and the water
does not flow.
D1
Set point too low so that the water
freezes.
D1.1
• Water does not pass;
• intake pressure too low.
Choose between:
• Raise the set point;
• add an appropriate % of
ethylene glycol (antifreeze)
(see
Chapter 5
“Installation“
).
D2
Evaporator obstructed by dirt carried by
the water to be cooled.
D2.1
High water temperature
difference between inlet and
outlet.
Depending on the type of dirt:
• clean the evaporator by
running a detergent solution
which is not aggressive for
steel, aluminium and
copper;
• run a high water flow
against the stream.
Install a filter upstream from
the
chille
r.
E
High pressure
switch (HP)
trips
E1
Fan does not work.
E1.1
The compressor
and the fan stop
Repair or replace the fan.
Where fitted, check the thermal
protection switch of the fan.
Press the reset button on the
cap of the pressure switch.
E2
Ambient air temperature too high.
E2.1
• Air ambient temperature higher
than maximum permitted value;
• See
E1.1
.
Reduce ambient temperature
within design limits, for
example by increasing local
ventilation.
Press the reset button on the
cap of the pressure switch.
E3
Recirculation of warm air due to incorrect
installation location.
E3.1
• Condenser cooling air
temperature higher than the
permitted value;
• See
E1.1
.
Change the position of the unit
or the position of any adjacent
obstructions to avoid
recirculation.
Press the reset button on the
cap of the pressure switch.
E4
See
A4
.
E4.1
See
E1.1
.
Clean the condenser fins.
Press the reset button on the
cap of the pressure switch.
E5
See
A5
.
E5.1
See
E1.1
.
Remove obstruction from
condenser intake.
Press the reset button on the
cap of the pressure switch.
E6
See
A1
.
E6.1
• Water outlet temperature too
high;
• refrigerant compressor stops.
Restore the thermal load to
within the preset limits.
Press the reset button on the
cap of the pressure switch.
Table 8
T
ROUBLE
SHOOTING