TAEevo M05-M10
12
The data inside this manual are not binding and they can be modified by the manufacturer without notice.
All rights reserved.
7.2.2 MEANING OF LEDs
The table below describes the LED functions:
NOTE
(*) the new value set is saved also when quitting without pressing the SET key.
7 . 3
D i s p l a y
The display is composed of 3 digits. Temperature detected by probe (-BT1) is displayed with decimal resolution, the field of display is: -
50÷110°C (-58÷230°F).
7 . 4
A u t o m a t i c r e - s t a r t
After a loss of power, the unit will re-start automatically if it was ON, observing the selected operating modality, but not if it was OFF before the
loss of power.
7 . 5
C o m p r e s s o r c o n t r o l
The compressor relay is activated to maintain a given temperature value
established by the set-point. Hysteresis Hy is automatically added to the set-
point. If the temperature value increases and reaches the set-point + hysteresis
value, the compressor is started and then stopped when the temperature value
returns to the set-point value. If the probe (-BT1) develops a fault, the
activation or deactivation of the output are managed by time by means of the
parameters “COn” and “COF”.
7 . 6
S t o r a g e t e m p e r a t u r e a l a r m
To view the minimum temperature reached:
Press
, the message "Lo" is displayed followed by the minimum temperature reached.
To view the maximum temperature reached:
Press
, the message "Hi" is displayed followed by the maximum temperature reached.
To delete the maximum or minimum temperature reached:
When the stored temperature value is displayed, hold down key
for several seconds (the flashing message "rSt" is displayed).
LED
MODE
MEANING
on
Compressor running
Flashing
Time lag between consecutive compressor starts
on
Defrost in progress (Not active function)
Flashing
Dripping in progress (Not active function)
B
on
Fans running (Not active function)
B
Flashing
Fan start delay in progress
on
Temperature alarm
on
Continuous cycle in progress
on
Energy saving in progress (Function not active)
/
on
Unit of measurement
/
Flashing
Programming
SET+HY
SET
Temper.
Time
Compr.
ON