PolyGard

®

 CO Transmitter

User Manual - LC-1112 V3

Page 06

5  Start-up operation 

Only trained technicians should perform the following: 

Check mounting location.

Check power voltage.

Check PCB for proper mounting at X4 and X5.

Verify transmitter operation (sensor/transmitter was factory calibrated).

Note:   

If calibration is necessary, the sensor element must be powered and be fully stabilized for at least 1 hour. 

Required instruments to calibrate the transmitter: 

Test gas bottle with synthetic air.

Test gas bottle with 200 ppm CO.

Gas pressure regulator with flow meter to control the gas flow to 150 ml/min.

Calibration set 

CONKIT-E/CH-LC

. See fig. 4.

Digital voltmeter with range 0 – 2 VDC, accuracy 1% and a small screwdriver.

Note: 

Please observe proper handling procedures for test gas bottles!  

5.1  Calibration 

Zero adjustment 

Zero-point calibration (4mA): 

(After sensor warm-up) 

Connect digital voltmeter to test pins – and + (with a range selected that will display 2 VDC max.).

Connect the calibration adapter to sensor element.

Apply sensor element zero calibration gas, (150 ml/min; 14.5 psi ± 10%), or other clean air source.

Wait two minutes until the signal is stable, adjust signal with zero potentiometer ”Zero” until the signal is 40

mV ± 3 mV and stable.

Remove calibration adapter carefully by turning lightly.

Specifications subject to change without notice. | USA 140916 | Page 6 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

LC-1112_V3 – UserManual

Polygard® is a registered trademark of MSR | UMLC1112I01

Specifications subject to change without notice. | USA 160104 | Page 6 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

LC-1112 V3 – UserManual

PolyGard

®

 is a registered trademark of MSR-Electronic GmbH | UMLC1112I01

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | UMLC1112I01 | USA 200211 | Page 6 of 13

LC-1112 V3 – UserManual

Содержание Intec Controls PolyGard CO LC-1112 V3

Страница 1: ...August 29 2006 Specifications subject to change without notice USA 140916 Page 1 of 13 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols LC 1...

Страница 2: ...oss sensitivity Data 9 9 Specifications 10 10 Wiring Configuration and Enclosure Dimensions 11 11 Notes and General Information 13 11 1 Intended product application 13 11 2 Installers responsibilities...

Страница 3: ...odes This signal is linear to the volume concentration of the sensed gas rather than the partial pressure The integrated two wire transformer converts this DC microampere signal to a standard 4 20 mA...

Страница 4: ...distribute several transmitters in a vertical and horizontal direction over the whole area to be monitored Avoid locations where water oil etc may influence proper operation and where mechanical dama...

Страница 5: ...minal strip X4 Connector 1 Power supply 24 VDC 17 28 VDC Connector 4 Signal 4 20 mA Connector 2 0 VDC DC common not needed 4 2 Wiring connection Unscrew cover of enclosure Unplug basic PCB from termin...

Страница 6: ...ttles 5 1 Calibration Zero adjustment Zero point calibration 4mA After sensor warm up Connect digital voltmeter to test pins and with a range selected that will display 2 VDC max Connect the calibrati...

Страница 7: ...ith a careful light turn Inspect the seating of the sensor element 5 2 Control span voltage calculation 160 mV x test gas concentration ppm 40 mV Measuring range CO ppm Example Measuring range CO conc...

Страница 8: ...se Unplug old sensor element out from the PCB Take new sensor element out of original packing Plug sensor element in the PCB Plug the PCB in terminal block X4 X5 carefully Calibrate after sensor warm...

Страница 9: ...20 ppm Hydrogen sulphide H2S 25 ppm 0 ppm Iso propanol C2H7OH 200 ppm 0 ppm Nitric oxide NO 50 ppm 8 ppm Nitrogen dioxide NO2 50 ppm 1 ppm Sulphur dioxide SO2 50 ppm 0 ppm Specifications subject to ch...

Страница 10: ...act GW Plast IEC 60695 2 12 GWFI 650 C fire retardant Enclosure color Light gray Protection NEMA12 IP 55 Installation Wall surface mounted or single gang electrical box Dimensions HxWxD 5 0 x 3 4 x 2...

Страница 11: ...COM1 X5 NC1 NO1 X6 P2 P1 Sensor 24 VDC_Inp 24VDC GND 24VDC OUT INP Bus_A Bus_B Calibration adapter Fig 4 Type CONKIT E CH LC Specifications subject to change without notice USA 140916 Page 11 of 13 1...

Страница 12: ...t to change without notice USA 140916 Page 12 of 13 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols LC 1112_V3 UserManual Polygard is a regi...

Страница 13: ...Any performance deviations may be serviced based on needed requirements Re calibration and part replacement may be implemented in the field by a qualified individual and with the appropriate tools Alt...

Отзывы: