PolyGard

®

 CO Transmitter

User Manual - LC-1112 V3

Page 10

9 Specifications 

Electrical

 

Power supply: 

17-28 VDC (polarity protected) 

Power consumption: 

22 mA, (0.6 VA), max. 

RFI/EMI protection 

5.0 W @1 ft. (0.31 m) radiated  

Sensor Performance

 

Gas detected 

Carbon monoxide (CO) 

Sensor element 

Electrochemical, diffusion 

Range 

0 – 250 ppm factory set 
0 - 200 to 0 – 300 ppm, adjustable via calibration 

Stability & resolution 

± 3.0 ppm of reading 

Repeatability 

± 3.0 % of reading 

Long term output drift 

 0.4% signal loss/month 

Response time 

t

90

 

 50 sec. 

Sensor life expectancy 

 

3-5 year, normal operating environment 

Sensor coverage 

5,000 sq.ft., (465 m

2

), to10,000 sq.ft. (930 m

2

) under “ideal conditions” 

Mounting height 

5 to 6 ft.  (1.5 to 1.8 m) above floor 

Type of Control 

Analog output signal 

Proportional, 4 – 20 mA, load 

 450 

 

Operating Environment

 

Working temperature  

14 °F to 122 °F  (-10 °C to + 50 °C) 

Intermitted temperature 

-4 °F to 122 °F (-20 °C to 50 °C) 

Storage temperature 

41 °F to 86 °F (5 °C to + 30 °C) 

Working humidity 

15 to 95% RH non-condensing 

Intermitted humidity 

0 to 99% RH non-condensing 

Pressure range 

Atmospheric ±10% 

Physical characteristics

 

Enclosure material 

High impact, GW-Plast, IEC 60695-2-12, GWFI-650 °C, fire-retardant 

Enclosure color 

Light gray 

Protection 

NEMA12 (IP 55) 

Installation 

Wall (surface) mounted or single gang electrical box 

Dimensions (HxWxD) 

5.0 x 3.4 x 2.2 in. (127 x 87 x 56 mm) 

Cable entry 

1 hole for ½ in. conduit for wall (surface) mounting, and 1 hole 
on back side of base plate for single gang electrical box mounting 

Wire connection 

Terminal blocks, screw type for lead wire 

Wire size 

Min. 24 AWG (0.25 mm

2

), max. 14 AWG (2.5 mm

2

Wire distance 

Max. loop resist. 500 

 (= wire resist. + controller input resist.) 

Weight 

0.6 Ibs. ( 0.25 kg ) 

Approvals/Listings

 

Unit rating 

NRTL Performance Tested & Certified, 

Conforms to STD ANSI/UL 2075 
City of Los Angeles 
CE 
VDI 2053, air treatment systems for garages and tunnels 

EMV-Compliance 89/336/EWG, 

low voltage directives 73/23/EWG 

Enclosure 

UL Listed, E208470 
CSA Certified, E208470 

Specifications subject to change without notice. | USA 140916 | Page 10 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

LC-1112_V3 – UserManual

Polygard® is a registered trademark of MSR | UMLC1112I01

Specifications subject to change without notice. | USA 160104 | Page 10 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

LC-1112 V3 – UserManual

PolyGard

®

 is a registered trademark of MSR-Electronic GmbH | UMLC1112I01

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | UMLC1112I01 | USA 200211 | Page 10 of 13

LC-1112 V3 – UserManual

Содержание Intec Controls PolyGard CO LC-1112 V3

Страница 1: ...August 29 2006 Specifications subject to change without notice USA 140916 Page 1 of 13 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols LC 1...

Страница 2: ...oss sensitivity Data 9 9 Specifications 10 10 Wiring Configuration and Enclosure Dimensions 11 11 Notes and General Information 13 11 1 Intended product application 13 11 2 Installers responsibilities...

Страница 3: ...odes This signal is linear to the volume concentration of the sensed gas rather than the partial pressure The integrated two wire transformer converts this DC microampere signal to a standard 4 20 mA...

Страница 4: ...distribute several transmitters in a vertical and horizontal direction over the whole area to be monitored Avoid locations where water oil etc may influence proper operation and where mechanical dama...

Страница 5: ...minal strip X4 Connector 1 Power supply 24 VDC 17 28 VDC Connector 4 Signal 4 20 mA Connector 2 0 VDC DC common not needed 4 2 Wiring connection Unscrew cover of enclosure Unplug basic PCB from termin...

Страница 6: ...ttles 5 1 Calibration Zero adjustment Zero point calibration 4mA After sensor warm up Connect digital voltmeter to test pins and with a range selected that will display 2 VDC max Connect the calibrati...

Страница 7: ...ith a careful light turn Inspect the seating of the sensor element 5 2 Control span voltage calculation 160 mV x test gas concentration ppm 40 mV Measuring range CO ppm Example Measuring range CO conc...

Страница 8: ...se Unplug old sensor element out from the PCB Take new sensor element out of original packing Plug sensor element in the PCB Plug the PCB in terminal block X4 X5 carefully Calibrate after sensor warm...

Страница 9: ...20 ppm Hydrogen sulphide H2S 25 ppm 0 ppm Iso propanol C2H7OH 200 ppm 0 ppm Nitric oxide NO 50 ppm 8 ppm Nitrogen dioxide NO2 50 ppm 1 ppm Sulphur dioxide SO2 50 ppm 0 ppm Specifications subject to ch...

Страница 10: ...act GW Plast IEC 60695 2 12 GWFI 650 C fire retardant Enclosure color Light gray Protection NEMA12 IP 55 Installation Wall surface mounted or single gang electrical box Dimensions HxWxD 5 0 x 3 4 x 2...

Страница 11: ...COM1 X5 NC1 NO1 X6 P2 P1 Sensor 24 VDC_Inp 24VDC GND 24VDC OUT INP Bus_A Bus_B Calibration adapter Fig 4 Type CONKIT E CH LC Specifications subject to change without notice USA 140916 Page 11 of 13 1...

Страница 12: ...t to change without notice USA 140916 Page 12 of 13 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols LC 1112_V3 UserManual Polygard is a regi...

Страница 13: ...Any performance deviations may be serviced based on needed requirements Re calibration and part replacement may be implemented in the field by a qualified individual and with the appropriate tools Alt...

Отзывы: