ManualNightFighterInstallation.doc
Prnt Spec. 10000005389(B) Mat. 10035581
07/23/02
Page 12 of 15
INSTALLATION MMR ICM 2000
REMOVING THE ICM
WARNING!
Do not disconnect the alarm coupling nut when pressure is shown on the harness gauge.
Always be sure that you have released all pressure from the regulator. Removing the
coupling nut with the regulator pressurized may result in serious personal injury or death.
Note:
All repair procedures assume that the alarm assembly is disconnected from the apparatus
cylinder.
1. Be sure the cylinder valve is completely closed.
2. Be sure that nothing blocks the regulator outlet. Open the bypass valve to relieve pressure in
the system.
REMOVING ICM FROM THE QUICK-FILL ADAPTER BLOCK
1. Use a wrench to hold the Quick Fill Adapter Block or place Quick Fill Adapter Block in a
vise using protective sleeves to keep from damaging the block.
2. Hold Quick-Fill Block with 5/8- inch wrench and slide the other wrench over Jam Nut and
loosen Jam Nut counter clockwise.
3. Unthread ICM unit from Quick Fill Adapter Block.
4. Remove and discard the Jam Nut.
Note:
Do not reuse the jam nut. Dispose of it immediately. Failure to follow this instruction
could result in personal injury.