Unit Installation

 Page 6

mrcool.com

3.1 Pre-Installation Instructions

3.1.1 Checking Product Received

          After receiving the product, please check it for damage that may have been caused during shipping.

          Shipping damage is the responsibility of the carrier. Verify the model number, specifications, and

          accessories are correct prior to installation. The distributor or manufacturer will not accept claims 

          from dealers for shipping damage or installation of incorrectly shipped units.

3.1.2  Before Installation

           Carefully read all instructions for the installation prior to beginning the installation. Make sure you

           understand each step or procedure and any special considerations are taken into account before

           starting the installation. Some tools or items for the installation may need to be purchased locally. 

           Make sure that everything that is needed to complete the installation is on hand before you begin.

3.1.3  Codes & Regulations

           This product is designed and manufactured to comply with national codes. It is the responsibility of 

           the installer to ensure that the product is installed in accordance with such codes and/or any

           prevailing local codes/regulations. The manufacturer assumes no responsibility for any equipment

           installed in violation of any codes or regulations. 

NOTE: The instructions contained within this manual are intended as a general guide and do not 

supersede local or national code in any way. Authorities who have jurisdiction should be 

consulted before installation.

3.1.4  Replacement Parts

           When reporting damages, shortages, or ordering replacement/repair parts, be sure to give the

           complete product model and serial numbers that are stamped on the product. Replacement parts for

           this product are available through your contractor or local distributor. 

3.2 Location

WARNING

This coil is designed for indoor installation only. 

DO NOT

 install it outdoors.

The coil drain pan has a maximum service temperature of 500°F (260°C). Close spacing 

may damage the drain pan and cause a leak. Please refer to the Product Specifications 

for the proper use of these coils with specific furnaces, air handlers, condensers, and 

line sets.

WARNING

The evaporator of the indoor unit is charged with refrigerant from the factory to 

maintain pressure. The cut-off valve can only be opened when the installation process 

and vacuuming procedure of the system have been completed. 

.

.

Содержание MDUCC15024

Страница 1: ...hank you for choosing MRCOOL Please read this manual carefully before installation and keep it for future reference Due to updates and constantly improving performance the information and instructions...

Страница 2: ...ting Evacuating and Charging 11 3 6 Ductwork 11 3 3 8 Sealing Ducts 11 Optional Quick Connect Line set Installation 10 3 3 A Coil Orientation Position Options 7 2 1 Product Description 4 2 2 Main Comp...

Страница 3: ...the requirements of the NEC and CEC by authorized personnel only Consult local building codes and NEC for special requirements The quali ed installer or agency must use factory authorized kits or acce...

Страница 4: ...RCOOL technical support at 270 366 0457 6 If the product is malfunctioning and or is inoperable please contact MRCOOL technical support at the aforementioned number as soon as possible and provide the...

Страница 5: ...erating sound levels and value for money The evaporator unit uses the environmentally friendly refrigerant R410A which is chlorine free to help prevent damage to the ozone layer 2 2 Main Components 2...

Страница 6: ...A B MDUCC15024 MDUCC15036 17 1 2 445 21 1 4 540 23 584 15 7 8 403 19 3 8 492 MDUCC15048 MDUCC15060 24 1 2 622 21 1 4 540 28 1 2 724 22 7 8 581 19 3 8 492 2 4 Cooling Capacity Range Cooling capacity ra...

Страница 7: ...talled in accordance with such codes and or any prevailing local codes regulations The manufacturer assumes no responsibility for any equipment installed in violation of any codes or regulations NOTE...

Страница 8: ...Application Return Air ow Supply Air ow to Ductwork A Coil Modular Blower Return Air ow Supply Air ow to Ductwork Up ow Application Return Air ow Supply Air ow to Ductwork Horizontal Right Application...

Страница 9: ...on pg 8 Once the line set installation is complete return to step 3 5 Condensate Removal and continue installation from there Solder Connection If connecting piping with solder make sure that any cuts...

Страница 10: ...it DO NOT connect the condensate drain pipe into a rain pipe as this could cause rain water to enter the unit and cause property damage and or personal injury The condensate drain pipe should be conne...

Страница 11: ...ctly as speci ed to avoid system leaks and or damage 9 At the OUTDOOR UNIT remove the protec ve cap at the cuto valve switch and open the cuto valve with a hex wrench to run the refrigera on circuit I...

Страница 12: ...stallation instructions provided with those units before the coil can be installed Position the cased coil on top of the furnace or air handler cabinet and secure it using eld provided screws NOTE If...

Страница 13: ...blower motor speed that will provide 300 450 CFM per 12 000 Btu h of cooling capacity wet coil Refer to the table 1 below for the recommended air ow volume Table 1 Cabinet Recommended Volume CFM Mode...

Страница 14: ...e life of the unit 5 1 Condensate Drain Pipe 5 2 Checklist Before Seasonal Use Check inlet outlet of indoor units for clogs Check that lter screen is securely in place Check that unit is securely inst...

Страница 15: ...Installation and rst run of the unit should be performed by professional personnel from a MRCOOL appointed service center The services of a professional are NOT required when the MRCOOL Quick Connect...

Страница 16: ...UNIVERSAL A Coils...

Отзывы: