Unit Installation

 Page 9

mrcool.com

The drain pan has a primary and secondary drain connection. Condensate removal is performed by 

attaching a 3/4 in (19 mm) pipe to the evaporator coil drain pan and is terminated in accordance with 

local or state plumbing/HVAC codes. The installation must include a “P” style trap that is located close to 

the evaporator coil. 

DO NOT 

overtighten the drain connection as this could damage or distort the 

drain pan and cause condensate leakage.

 Please refer to the guidelines and illustration below to best 

determine how and where to run the condensate drain pipe

 

DO NOT

 

connect the condensate drain pipe into a waste pipe or other pipelines which are

 

likely to produce corrosive fumes or an odor. Connecting to these pipes could cause the

 

fumes or odor to enter indoors and/or corrupt the unit.

 

DO NOT

 connect the condensate drain pipe into a rain pipe, as this could cause rain water

 

to enter the unit and cause property damage and/or personal injury.

 

The condensate drain pipe should be connected into a drain system specifically for the unit.

          

          

Screw Connection

         C

onnect the pipe to the unit. Follow all instructions below. Use both a spanner and torque wrench. When

         connecting the tapered screw nut, first apply Polyolester oil (POE oil) on its inner and outer surface. Then,

         screw the first 3 or 4 threads by hand. Next, tighten the nut with the spanner and torque wrench. Confirm 

         the tightening torque by referring to the following table. 

DO NOT

 overtighten the nut as it could damage 

         it and cause the connection to leak.

 

Keep pipe connection exposed to perform the leak test.

          

Pipe diameter (inch)

Tightening torque: ft-lbs (N·m)

1/4 in

11-22 ft-lbs (15-30 N·m)  

3/8 in

26-30 ft-lbs (35-40 N·m) 

1/2 in

33-37 ft-lbs (45-50 N·m) 

5/8 in

44-48 ft-lbs (60-65 N·m)

3/4 in

52-55 ft-lbs (70-75 N·m) 

7/8 in

59-63 ft-lbs (80-85 N·m)

3.5 Condensate Removal

.

Содержание MDUCC15024

Страница 1: ...hank you for choosing MRCOOL Please read this manual carefully before installation and keep it for future reference Due to updates and constantly improving performance the information and instructions...

Страница 2: ...ting Evacuating and Charging 11 3 6 Ductwork 11 3 3 8 Sealing Ducts 11 Optional Quick Connect Line set Installation 10 3 3 A Coil Orientation Position Options 7 2 1 Product Description 4 2 2 Main Comp...

Страница 3: ...the requirements of the NEC and CEC by authorized personnel only Consult local building codes and NEC for special requirements The quali ed installer or agency must use factory authorized kits or acce...

Страница 4: ...RCOOL technical support at 270 366 0457 6 If the product is malfunctioning and or is inoperable please contact MRCOOL technical support at the aforementioned number as soon as possible and provide the...

Страница 5: ...erating sound levels and value for money The evaporator unit uses the environmentally friendly refrigerant R410A which is chlorine free to help prevent damage to the ozone layer 2 2 Main Components 2...

Страница 6: ...A B MDUCC15024 MDUCC15036 17 1 2 445 21 1 4 540 23 584 15 7 8 403 19 3 8 492 MDUCC15048 MDUCC15060 24 1 2 622 21 1 4 540 28 1 2 724 22 7 8 581 19 3 8 492 2 4 Cooling Capacity Range Cooling capacity ra...

Страница 7: ...talled in accordance with such codes and or any prevailing local codes regulations The manufacturer assumes no responsibility for any equipment installed in violation of any codes or regulations NOTE...

Страница 8: ...Application Return Air ow Supply Air ow to Ductwork A Coil Modular Blower Return Air ow Supply Air ow to Ductwork Up ow Application Return Air ow Supply Air ow to Ductwork Horizontal Right Application...

Страница 9: ...on pg 8 Once the line set installation is complete return to step 3 5 Condensate Removal and continue installation from there Solder Connection If connecting piping with solder make sure that any cuts...

Страница 10: ...it DO NOT connect the condensate drain pipe into a rain pipe as this could cause rain water to enter the unit and cause property damage and or personal injury The condensate drain pipe should be conne...

Страница 11: ...ctly as speci ed to avoid system leaks and or damage 9 At the OUTDOOR UNIT remove the protec ve cap at the cuto valve switch and open the cuto valve with a hex wrench to run the refrigera on circuit I...

Страница 12: ...stallation instructions provided with those units before the coil can be installed Position the cased coil on top of the furnace or air handler cabinet and secure it using eld provided screws NOTE If...

Страница 13: ...blower motor speed that will provide 300 450 CFM per 12 000 Btu h of cooling capacity wet coil Refer to the table 1 below for the recommended air ow volume Table 1 Cabinet Recommended Volume CFM Mode...

Страница 14: ...e life of the unit 5 1 Condensate Drain Pipe 5 2 Checklist Before Seasonal Use Check inlet outlet of indoor units for clogs Check that lter screen is securely in place Check that unit is securely inst...

Страница 15: ...Installation and rst run of the unit should be performed by professional personnel from a MRCOOL appointed service center The services of a professional are NOT required when the MRCOOL Quick Connect...

Страница 16: ...UNIVERSAL A Coils...

Отзывы: