Page 1
mrcool.com
4
Blower Speed Selection
Page 12
mrcool.com
Proper air volume must be provided over the evaporator coil. Select a blower motor speed that will
provide 300-450 CFM per 12,000 Btu/h of cooling capacity (wet coil). Refer to the table 1 below for the
recommended airflow volume.
Table 1
Cabinet
Recommended Volume
(CFM)
Model
Width
inch (millimeter)
MDUCC15024/
MDUCC15036
17.5 (444.5)
800
17.5 (444.5)
1000
MDUCC15048/
MDUCC15060
24.5 (622.3)
1230
24.5 (622.3)
1510
Содержание MDUCC15024
Страница 16: ...UNIVERSAL A Coils...