XIV. System Self-adjustment
When the temperature control effect is not ideal, the user
can perform system self-adjustment. In the process of
self-adjustment, there will be a large overshoot of temperature,
and users should fully consider this factor before performing
system self-adjustment.
In the non-setting state, press and hold the “ Add/
Self-adjustment” button for 5 seconds to enter the system
Self-adjustment procedure. The “self-adjustment” indicator
flashes. After the self-adjustment is over, the indicator light
is on and the controller will get a new set of system PID
parameters, which are automatically saved, and the controller
automatically switches to the temperature control state. In the
process of system self-adjustment, after pressing the
“Add/Auto-tuning” button for 5 seconds, you can terminate the
self-adjustment process.
If there is a second set over-temperature alarm during
system self-adjustment, the heating alarm relay will be
automatically disconnected. The "set" button is valid during
the system self-adjustment process.
Note: To do self-adjustment, turn on the “Heating Allow