13 Technical data
58
5809776/02 EN
13.6 Standards and directives
Electromagnetic compatibility
IEC
61000-4-2
Immunity to electrostatic discharge (ESD)
▪ Contact: ±4 kV
▪ Air: ±8 kV
IEC 61000-4-3
Immunity to high-frequency electromagnetic fields
▪ 10 V/m; 80...3000 MHz; 80% AM
IEC 61000-4-4
Immunity to quick, transient electrical disturbances
(burst)
▪ Power supply: 2 kV
▪ Communication interfaces: 1 kV
IEC 61000-4-5
Immunity to impulse voltages (surge)
▪ Power supply: 500 V
▪ Communication interfaces: 1 kV
IEC 61000-4-6
Immunity to conducted disturbances, induced by high-
frequency fields
▪ 10 V, 150 kHz...80 MHz, 80% AM
IEC 61000-4-8
Immunity to power frequency magnetic fields
▪ 100 A/m, 50/60 Hz, continuously
IEC 61000-4-9
Immunity to pulse magnetic fields
▪ 1000 A/m, 50/60 Hz, continuously
Table 21: Immunity in accordance with IEC 61000-6-2
CISPR 16-2-1
Procedure for measuring high-frequency emitted inter-
ference (radio interference) and immunity - measure-
ment of conducted emitted interference: Class A
CISPR 16-2-3
Procedure for measuring high-frequency emitted inter-
ference (radio interference) and immunity - measure-
ment of radiated emitted interference: Class A
CISPR 22 (EN 55022)
Information technology equipment - Radio disturbance
characteristics - Limits and methods of measurement:
Class A
Table 22: Emitted interference in accordance with IEC 61000-6-4
Содержание MControl 10
Страница 1: ...Touch Panel MControl 7 10 Operating Instructions 5809776 02 EN ...
Страница 32: ...6 Mounting 32 5809776 02 EN Figure 9 Inserting the device into the cut out ...
Страница 37: ...6 Mounting 37 5809776 02 EN 4 Connect the power supply Figure 16 Connecting the power supply ...
Страница 54: ...12 Disposal 54 5809776 02 EN Observe the national requirements applicable in the country of use ...
Страница 60: ......
Страница 61: ......