mr.steam
®
Installation, Operation & Maintenance Manuals
______________________________________________________________________________
I
N
S
T
A
L
L
E
R
10
DRAIN
(1" NPT)
Applies to 1-3
1. Do not connect the generator drain line to an
undersink trap.
2. Do not drain into a steam enclosure or any location where
accidental contact with drain water may occur. In the event
of a power failure the AutoFlush valve will open and may
discharge boiling water causing a scalding hazard.
3. Do not connect the drain valve to the steam piping.
Connecting the drain line to the steam piping may allow
boiling water to discharge through the steamhead causing
a scalding hazard.
Applies to 4-8
4. A drain valve is provided to facilitate maintenance and
servicing. Provide a drain line connection from steambath
generator drain valve according to National and Local Codes.
5. Check local plumbing code for receptor, trap and vent
requirements.
6. Do not connect Drain line and Safety Valve line together.
7. The steam generator drains by gravity. Plumb all drain lines
accordingly.
8. See page 20 for installation of the optional Condensation
Pan.
SAFETY VALVE
(
3
⁄
4
" NPT)
Where permitted by local codes, provide an outlet plumbing
connection for safety valve.
Applies to 1-3
1. To insure proper and automatic safety valve operation do not
connect a shut off valve or a plug at safety valve outlet.
2. Do not connect a shut off valve or any obstruction
to the safety valve.
3. Do not connect the safety-valve output to the steam piping.
AROMASTEAM
If the optional AromaSteam Fragrance Delivery
System (
PN
:
MS AROMA
) is to be installed, a 90 degree
T
plumb-
ing fitting must be installed at a designated location on the
steam piping. See the MrSteam AromaSteam Operation and
Instruction Manual (
PN
: 100402) for installation information
before the steam piping is installed at the technical downloads
section of www.mrsteam.com.
PLUMBING
GENERAL
1. All plumbing shall be performed by a qualified licensed
plumber and in accordance with applicable National
and local codes.
Applies to 2-4
2. Use unions on all pipe connections as required for serv-
ice and removal of the steam generator.
3. Use only brass piping or rigid copper tubing. Use only
piping as permitted by codes.
4. Do not use black, galvanized, PVC pipe or PEX except
as noted below.
Applies to 1-9
1. Install a shut off valve in the water supply line.
2. It is recommended to install a strainer in the water
supply line.
3. Install an anti-water hammer device as required.
4. Install an approved backflow preventer as required by
local codes.
5. Connect the generator to a cold water line.
6. Water feed line may be flexible copper tubing, braided
hose, PVC or PEX if permissible by local codes.
7. Do not overheat inlet solenoid valve with solder con-
nections. Overheating will damage parts and result in
a water leak.
8. Flush inlet water line thoroughly before making
connection to the generator.
9. To reduce operating noise, reduce feed water pressure
to between 15 - 20 psi is recommended. Optional
pressure reducing valve part number 104198.
MX4E-6E
Water Inlet
3
⁄
8
” NPT
Steam Outlet
3
⁄
4
” NPT
Safety Valve
3
⁄
4
” NPT
Manual Drain Valve
1" NPT
AutoFlush Valve
1" NPT
Water supply and steam piping must be
flushed to remove flux and other debris prior to
connecting the steam generator. Failure to flush the
steam piping may result in flux poisoning or a ha
z
ardous
condition. Failure to flush the steam piping may result in
blockage or an inoperable system.
WATER
SUPPLY
(
3
⁄
8
"
NPT)
Plumbing Specifications