background image

8

Transformer

Liquid Level
Control Board

Water Feed

 Solenoid

Water Feed

Thermostat

Liquid Level Probe

Power Block

Power Supply

Knock-Out

Contactor

Steam Outlet

Fuses

AutoFlush Plug and 
Play Connector

(see page 11)

Transformer

Liquid Level
Control Board

Water Feed

 Solenoid

Water Feed

AutoFlush Plug and 
Play Connector

(see page 11)

Thermostat

Liquid Level Probe

Power Supply

Knock-Out

Contactor

Steam Outlet

FIELD POWER WIRING

TO AVOID EQUIPMENT DAMAGE DO
NOT CONNECT POWER SUPPLY
DIRECTLY TO ELEMENTS!!!

L1, L2, GROUND TO BE FIELD WIRED

NOTE: FOR ILLUSTRATIVE PURPOSES
ONLY. CONSULT WITH QUALIFIED
LICENSED ELECTRICIAN FOR 
ELECTRICAL INSTALLATION.

Models CT6E – CT9E

(single phase wiring shown)

Models CT

12

E

(single phase wiring shown)

ELECTRICAL

All electrical wiring to be installed by a qualified licensed electrician
in accordance with National Electrical Code and local electrical code.

Power Wiring- 

See “Field Power Wiring” Diagrams (below)

1.

Check power voltage. Use 240V rated unit when supply is greater

than 208V. Use 208V rated unit for 208V power.

2. 

Use minimum 90˚ C/300V rated insulated copper conductors only,

sized in accordance with National Electrical Code and local electri-
cal code for the current in Ampere Chart. If allowed by codes, NM
cable may require a larger wire size than as listed on the chart.

3. 

Connect suitably sized equipment grounding wire to ground termi-

nal provided.

4.

Install a separate circuit breaker between supply and unit.  Provide

a power supply disconnect within sight of the steam generator or
one that is capable of being locked in the open position.

5.

For single phase units, use two-wire supply source and equipment

grounding wire. Neutral (white) wire is not required.

CHART

________________________________________________________________________

MODEL

MAX ROOM

KW

VOLTS

WIRE SIZE

NO.

VOL 

(CU. FT.*)

1

PH

PHASE

AMPS

(AWG)

________________________________________________________________________

208

1

29

8

CT6E

150

6.0

3

17

10

________________________________________

240

1

25

8

3

14

12

________________________________________________________________________

208

1

44

8

CT9E

360

9.0

3

25

8

________________________________________

240

1

38

8

3

22

10

________________________________________________________________________

208

1

58

6

CT2E

575

12.0

3

34

8

________________________________________

240

1

50

6

3

29

8

________________________________________________________________________

*See page 2 for room sizing.

All specifications shown are for 208V and 240V. 

Consult factory for other voltage specifications. 

mr

.

steam

®

club therapy

®

Installation, Operation & Maintenance Manual

______________________________________________________________________________

!

WA R N I N G

Provide a power supply disconnect within sight of the steam generator or one
that is capable of being locked in the open position as permitted by code.

Содержание CT12E

Страница 1: ...mr steam club therapy Club Therapy Steambath Generator Systems Installation Operation Maintenance Manual Models CT 6E CT 9E CT 12E...

Страница 2: ...mbing Water Supply Drain Steam Outlet Safety Valve Drain Pan AromaSteam 5 Steam Head Installation 6 Generator Dimensions 7 Electrical Specifications Field Power Wiring 8 Wiring Diagrams 9 10 Initial S...

Страница 3: ...h the steam head and avoid the steam near the steam head C Prolonged use of the steam system can raise excessively the internal human body temperature and impair the body s ability to regulate its int...

Страница 4: ...isclaims responsibility for the sizing of a model selected IMPORTANT For steam rooms constructed of acrylic or synthetic materials select next lower rated CT model WARNING In considering a purchase of...

Страница 5: ...dripping of condensate If acrylic fiberglass or other non heat resistant materials are used as part of the steam room enclosure Consult with the material manufac ture and see pg 6 Steamhead for additi...

Страница 6: ...with bathers NOTE FOR ILLUSTRATIVE PURPOSES ONLY Consult with qualified designer architect or contractor for steam room construction details Provide unions as required to facilitate installation and d...

Страница 7: ...AutoFlush valve automatically will open and drain the generator Steam Outlet 1 2 NPT 1 Do not install any valve in steam line Flow of steam must be unobstructed 2 Use 1 2 inch brass pipe or copper tub...

Страница 8: ...rary nipple 6 or longer in the drop ear fitting to locate the steamhead after the wall is finished STEP 4 After the wall has been finished mark on the nipple where the surface of the wall is Remove th...

Страница 9: ...nal AutoFlush 2 All units in inches MM Water Inlet Control Accessory Connections Steam Outlet Safety Valve AutoFlush Manual Drain Valve IMPORTANT NOTE Provide a minimum of 12 inches at both ends and t...

Страница 10: ...bly sized equipment grounding wire to ground termi nal provided 4 Install a separate circuit breaker between supply and unit Provide a power supply disconnect within sight of the steam generator or on...

Страница 11: ...ARD CONTACTOR HEATING ELEMENT TO PROBE AUTOFLUSH CT STEAMSTOP ET PLUS CONTROL TRANSFORMER POWER INPUT L1 L2 FUSES GROUND WATER FEED SOLENOID VALVE EXPRESS STEAM THERMOSTAT HEATER FACTORY WIRING FIELD...

Страница 12: ...LUS CT STEAM STOP and MSTS WARNING CAUTION mr steam clubtherapy Installation Operation Maintenance Manual ______________________________________________________________________________ FACTORY WIRING...

Страница 13: ...into a steam enclosure or any location where accidental contact with drain water may occur In the event of a power failure the AutoFlush System valve will open and may discharge boiling water Sweat F...

Страница 14: ...n there is 208 240 Volt incoming power connected 24 Volt transformer secondary output and on board 5 Volt DC control power are present _________________________________________________________________...

Страница 15: ...s not related to component identification Models CT12E shown with cover removed NOTE FOR ILLUSTRATIVE PURPOSES ONLY Some components may be omitted or altered for clarity Do not use for wiring repair o...

Страница 16: ...pole All 3 Phase models 103453 Contactor 50A 4 pole CT12E 100471 2 Probe Assembly All models 99096MS Heating Element Gasket All models 103938 Acrylic Shield All Models 99314 Power Fuse 60A 250V CT12E...

Страница 17: ...sired steambathing temperatures Do not locate the control above or near the steam head or direct steam emissions Failure to install according to instruc tions will result in an inoperative control and...

Страница 18: ...steam head or direct steam emissions IMPORTANT See installation instructions for the MSTS Temperature Probe before rough in or installation of control pgs 19 20 Step 2 Make a one inch diameter hole i...

Страница 19: ...ICONE TO ANY OTHER PARTS OF THE CONTROL INCLUDING THE ADHESIVE GASKET Step 7 Insure the mounting surface is clean and dry as required for good adhesion Apply silicone into the hole in the wall as requ...

Страница 20: ...EP 3 Diagram 4 Remove and discard the peel off paper from the switch housing to expose the adhesive as shown in Diagram 4 STEP 4 Diagram 5 Apply silicone provided with eTEMPO PLUS control to the hole...

Страница 21: ...atures Do not locate the MSTS above or near the steam head or direct steam emissions The probe has an integral 60 cable Insure that the probe and or steam generator are located accordingly 2 Drill a 5...

Страница 22: ...xposed as shown below Insure a minimum of 1 4 of the temperature bulb is exposed to the air Failure to do so may result in an inopera tive control and a hazardous condition The exposed area of the tem...

Страница 23: ...the control is turned ON The duration required for the steam room to reach steambathing temperatures depends on the steam room construction and steam generator specifications Steam may continue to flo...

Страница 24: ...20 minutes and 110 F will be used the next time the control is turned on If the control times out not manually turned off then the previous user time and temperature settings will be used when the ste...

Страница 25: ...uge strength and suitability Limit to a maximum of a few drops for a steambathing session The bather should exit the steambath IMMEDIATELY if dizziness occurs If skin irritation occurs stop using the...

Страница 26: ...O Plus controls according to installation instructions Failure to install according to instructions will result in an inoperative control or hazardous overheating or inadequate heating of the steam ro...

Страница 27: ...LUB THERAPY eTEMPO eTEMPO PLUS FROM BATHROOM TO SPA MAKING WELLNESS A WAY OF LIFE MUSICTHERAPY STEAM HOME STEAM ON DEMAND STEAMTHERAPY and SUSSMAN are registered trademarks of Sussman Automatic Corpor...

Отзывы: