Installation Instructions and Owner’s Manual

Unvented Natural Gas Fired Room Heater

• 

If pilot does not stay lit, refer to Troubleshoot

-

ing, pages 14 & 15. Also, contact a qualified 

service person of gas supplier for repairs. 

• 

If control knob does not pop up when released, 

contact a qualified service person or gas sup

-

plier for repairs.

8.

 

  When the pilot is lit, turn control knob coun

-

terclockwise to heating level. The main burner 

should light.

9.  To select the desired heat level, turn the 

temperature setting knob counterclockwise to 

between 1 & 5. 

THERMOSTAT CONTROL OPERATION

FOR IR20NGT / IR30NGT:

 The thermostatic control 

used simply turns on and off the burner. 

FOR BF20NGT / BF30NGT: 

The thermostatic control 

used modulates the flame size as the temperature gets 

closer to set point, then it turns off the burner upon 

reaching temperature.
The burner will cycle back on when room temperature 

drops below the set temperature. The control knob can 

be set to any heat level between 1 and 5. Selecting the 

HI setting will cause the burner to remain on.

Note: The thermostat sensing bulb measures the 

temperature of air near the heater cabinet. This may 

not always agree with room temperature (depend-

ing on housing construction, insulation location, 

room size, open air temperature, etc.). Frequent 

use of your heater will let you determine your own 

comfort levels.

The LED temperature indicator measures approximate 

room temperature around the heater. 

Note:

 The LED temperature indicator 

DOES NOT

 oper

-

ate with or control the thermostat setting of the heater.

TO TURN OFF GAS TO APPLIANCE

SHUTTING OFF HEATER

1.  Turn control knob clockwise to the OFF posi

-

tion.

2.  Turn off all electrical power to the appliance if 

servicing is to be preformed.

3.  Turn off equipment shutoff valve.

SHUTTING OFF BURNER ONLY (PILOT STAYS LIT)

1.  Turn control knob clockwise to the PILOT/IGN 

position.

INSPECTING BURNER

Check pilot flame pattern and burner flame pattern 

often.

PILOT FLAME PATTERN

Figure 21 show a correct pilot flame pattern. Figure 22 

shows an incorrect pilot flame pattern. The incorrect 

pilot flame pattern is not touching thermocouple. This 

will cause the thermocouple to cool. When the thermo

-

couple cools, the heater will shut down. If pilot flame 

pattern is incorrect, as shown in Figure 22:

• 

Turn heater off (see 

To Turn OFF Gas to Ap-

pliance

, page 11 for non-thermostat models or 

page 12 for thermostat models).

• 

See Troubleshooting, pages 14 and 15.

BURNER FLAME PATTERN

Figure 23 show a correct burner flame pattern. Figure 

24 shows an incorrect burner flame pattern. If burner 

flame pattern is incorrect, as shown in Figure 24:

• 

Turn heater off (see To Turn OFF Gas to Ap

-

pliance, page 11 for non-thermostat models or 

page 12 for thermostat models).

• 

See Troubleshooting, pages 14 and 15. 

Figure 23a. 

Figure 23b. 

Figure 24a.

Figure 21

Figure 22

Содержание HeatStar HSBF20NGT

Страница 1: ...ier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Pro visions for adequate combustion and ventilation air must be provided Refer to Fresh Air for Combustion and V...

Страница 2: ...fresh air at once Have heater serviced Some people are more affected by carbon monoxide than oth ers These include pregnant women persons with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes Natural Gas Raw natural gas is odorless An odor making agent is added to natural gas which helps you detect a natural gas leak However the odor added to natural...

Страница 3: ...R COMBUSTION AND VENTILATION WARNING This heater shall not be installed in a confined space or unusually tight construction un less provisions are provided for adequate combus tion and ventilation air Read the following instruc tions to insure proper fresh air for this and other fuel burning appliances in your home ESTABLISHING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas...

Страница 4: ...er gas appliances Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors Example Gas water heater 40 000 Btu hr Vent Free Heater 20 000 Btu hr Total 60 000 Btu hr 4 Compare the maximum Btu hr the space can support with the actual amount of Btu hr used Example 51 800 Btu hr maximum Btu hr the space can support 60 000 Btu hr Actual amou...

Страница 5: ...dy or drafty areas WARNING Heater must be mounted to maintain the minimum clearances shown in Figure 4 If pos sible provide greater clearances from the floor ceil ing and joining walls Figure 3 Ventilation from Outdoors If necessary provide extra fresh air by using ventila tion grills or ducts Connect these items directly to the outdoors or spaces open to the outdoors These include attics and craw...

Страница 6: ...ill be located Make sure mounting bracket is level For wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in figure 7 If you can provide greater clearances from the floor and joining wall 2 Mark screw locations on wall see figure 7 3 Remove tape and mount bracket from wall Figure 7 Attaching to Wall Stud For attaching mounting brack...

Страница 7: ... installing bottom mounting screw into wall stud drill holes at marked locations using 9 64 drill bit 5 Re place heater onto mounting bracket 6 Place spacers between bottom mounting holes and wall anchor or drilled hole 7 Hold spacer in place with one hand With the other hand insert mounting screw through bottom mounting hole and spacer Place tip of screw in opening of wall anchor or drilled hole ...

Страница 8: ...inet Ground Joint Union Equipment Shutoff Valve From Gas Meter 4 W C to 10 5 W C Pressure Tee Joint 1 8 NPT Plug Tap Cap Pipe Nipple Tee Joint 3 8 NPT Pipe Nipple Sediment Trap Test Gauge Connection Reducer Bushing to 1 8 NPT 3 Minimum taminants This keeps them from going into heater If sediment trap is not installed or is installed improperly heater may not run correctly IMPORTANT Hold pressure r...

Страница 9: ... floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call you gas supplier from a neigh bor s phone Follow the gas supplier s instruc tions If you can not reach your gas supplier call the fire department Pressure Testing Heater Gas Connections 1 Make sure that the heater supply piping sys tem is co...

Страница 10: ...30 seconds This will allow air to bleed from the gas system 6 Push in control knob and rotate control knob back to OFF position then rotate counterclock wise to PILOT IGN position This will light pilot If needed gently keep rotating control knob back and forth while depressed until pilot lights 7 Keep control knob depressed in for ten 10 seconds after lighting pilot If pilot goes out repeat steps ...

Страница 11: ...ing control knob Control knob must be locked at the desired position TO TURN OFF GAS TO APPLIANCE SHUTTING OFF HEATER 1 Turn control knob clockwise to the OFF posi tion 2 Turn off all electrical power to the appliance if servicing is to be preformed 3 Turn off equipment shutoff valve SHUTTING OFF BURNER ONLY PILOT STAYS LIT 1 Turn control knob clockwise to the PILOT IGN position OPERATING YOUR HEA...

Страница 12: ...ll let you determine your own comfort levels The LED temperature indicator measures approximate room temperature around the heater Note The LED temperature indicator DOES NOT oper ate with or control the thermostat setting of the heater TO TURN OFF GAS TO APPLIANCE SHUTTING OFF HEATER 1 Turn control knob clockwise to the OFF posi tion 2 Turn off all electrical power to the appliance if servicing i...

Страница 13: ...t you keep the burner tube and pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 psig This can be done by using a vacuum cleaner in the blow position using compressed air in a can please follow the directions on the can If you don t follow directions on the can you could damage the burner or pilot assembly In addition the direc...

Страница 14: ...ol valve damaged 1 Burner orifice is clogged 2 Burner orifice diameter to small 3 Inlet gas pressure is too low 1 Manifold pressure is too low 2 Burner orifice is clogged When ignitor button is pressed in there is no spark at pilot ODS pilot lights but flame goes out when control knob is released When ignitor button is pressed in there is a spark at the ODS pilot but no ignition Burner does not li...

Страница 15: ...l leaks see Checking Gas Connections page 8 1 This is common with most heaters If noise is excessive contact qualified service person 1 Refer to Fresh Air for Combustion and Ventilation page 3 through 5 Heater produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during combustion Heater produces a clicking tick ing noise just afte...

Страница 16: ... 36 915cm Sides 6 152cm 10 5 267cm 10 5 267cm Floor min to top of carpet 2 51cm 2 51cm 2 51cm Fabric flammable objects 36 915cm 36 915cm 36 915cm BF6NG BF10NG BF20NGT BF30NGT BTU Available 6 000 10 000 20 000 30 000 Type of Gas Natural Gas Only Natural Gas Only Natural Gas Only Ignition Piezo Battery ignitor 1 AA Battery ignitor 1 AA Pressure Regulator Setting 4 5 Inches of Water 4 5 Inches of Wat...

Страница 17: ...17 Installation Instructions and Owner s Manual Unvented Natural Gas Fired Room Heater ...

Страница 18: ...18 Installation Instructions and Owner s Manual Unvented Natural Gas Fired Room Heater ...

Страница 19: ...19 Installation Instructions and Owner s Manual Unvented Natural Gas Fired Room Heater ...

Страница 20: ...20 Installation Instructions and Owner s Manual Unvented Natural Gas Fired Room Heater ...

Страница 21: ...21 Installation Instructions and Owner s Manual Unvented Natural Gas Fired Room Heater ...

Страница 22: ...pe of gas used Natural Gas Purchase date Usually we will ask you to return the defective part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealer of this product If they can t supply original replacement part s call Enerco Group Inc s 800 on the back of this manual TECHNICAL SERVICE You may have further questions about installation operation or troubleshooting if so contact Enerco Gr...

Страница 23: ...23 Installation Instructions and Owner s Manual Unvented Natural Gas Fired Room Heater Notes ...

Страница 24: ...parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such costs related to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRA...

Отзывы: