PAGE 40 — DCA-180SSK — PARTS AND OPERATION MANUAL — REV. #3 (06/11/09)
Outdoor Installation
Install the generator in a location where it will not be exposed
to rain or sunshine. Make sure the generator is on secure
level ground so that it cannot slide or shift around. Also
install the generator in a manner so the exhaust will not be
discharged in the direction of nearby homes.
The installation site must be relatively free from moisture
and dust. All electrical equipment should be protected from
excessive moisture. Failure to do will result in deterioration
of the insulation and will result in short circuits and grounding.
Foreign materials such as dust, sand, lint and abrasive
materials have a tendency to cause excessive wear to the
engine parts and the alternator.
CAUTION :
Pay close attention to ventilation when
operating the generator inside tunnels and
caves. The engine exhaust contains
noxious elements. Engine exhaust must
be routed to a ventilated area.
Indoor Installation
Exhaust gases from diesel engines are extremely poisonous.
Whenever an engine is installed indoors the exhaust fumes
must be vented to the outside. The engine should be installed
at least two feet from any outside wall. Using an exhaust
pipe which is too long or too small can cause excessive
back pressure which will cause the engine to heat
excessively and possibly burn the valves.
CAUTION :
An electric shock may happen when
vibrators are used. Pay close attention
to handling when operating vibrators and
always use rubber boots and gloves to
insulate the body from electrical shock.
Generator Grounding
To guard against electrical shock and possible damage to
the equipment, it is important to provide a good
EARTH
ground.
Article 250 (Grounding) of the National Electrical Code (NEC)
provides guide lines for proper grounding and specifies that
the cable ground shall be connected to the grounding system
of the building as close to the point of cable entry as
practical.
NEC articles 250-64(b) and 250-66 set the following
grounding requirements:
1. Use one of the following wire types to connect the
generator to earth ground.
a. Copper - 10 AWG (5.3 mm
2
) or larger.
b. Aluminum - 8 AWG (8.4 mm
2
) or larger.
2. When grounding the generator (Figure 27) connect the
ground cable between the lock washer and the nut on
the generator and tighten the nut fully. Connect the other
end of the ground cable to earth ground.
3. NEC article 250-52(c) specifies that the earth ground
rod should be buried a minimum of 8 ft. into the ground.
When connecting the generator to
any buildings electrical system
ALWAYS
consult with a licensed
electrician.
NOTE
DCA-180SSK — INSTALLATION
Содержание WHISPERWATT DCA180SSK
Страница 2: ...PAGE 2 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 PROPOSITION 65 WARNING ...
Страница 3: ...DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 PAGE 3 NOTE PAGE ...
Страница 22: ...PAGE 22 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 DCA 180SSK OPERATION AND SAFETY DECALS ...
Страница 23: ...DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 PAGE 23 DCA 180SSK OPERATION AND SAFETY DECALS ...
Страница 24: ...PAGE 24 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 DCA 180SSK OPERATION AND SAFETY DECALS ...
Страница 30: ...PAGE 30 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 DCA 180SSK CONTROL PANEL Figure 8 Control Panel ...
Страница 58: ...PAGE 58 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 DCA 180SSK GENERATORWIRING DIAGRAM ...
Страница 59: ...DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 PAGE 59 DCA 180SSK ENGINEWIRING DIAGRAM ...
Страница 66: ...PAGE 66 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 GENERATOR ASSY DCA 180SSK GENERATOR ASSY ...
Страница 68: ...PAGE 68 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 DCA 180SSK CONTROL PANEL ASSY CONTROL PANEL ASSY ...
Страница 70: ...PAGE 70 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 DCA 180SSK CONTROL BOX ASSY CONTROL BOX ASSY ...
Страница 78: ...PAGE 78 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 DCA 180SSK BATTERY ASSY BATTERY TERMINAL ASSY ...
Страница 80: ...PAGE 80 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 DCA 180SSK MUFFLER ASSY MUFFLER ASSY ...
Страница 82: ...PAGE 82 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 DCA 180SSK FUELTANK ASSY ...
Страница 84: ...PAGE 84 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 DCA 180SSK ENCLOSURE ASSY ENCLOSURE ASSY ...
Страница 86: ...PAGE 86 DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 DCA 180SSK ENCLOSURE ASSY ENCLOSURE ASSY ...
Страница 97: ...DCA 180SSK PARTS AND OPERATION MANUAL REV 3 06 11 09 PAGE 97 NOTE PAGE ...