PAGE 38 — DCA-70USI (60 Hz) — OPERATION AND PARTS MANUAL — REV. #0 (01/04/06)
Shutdown Procedure
To shutdown the generator use the following procedure:
1. Place both the
MAIN
,
GFCI
and
LOAD
circuit breakers
as shown in Figure 39 to the
OFF
position.
3. Let the engine cool by running it for 3-5 minutes with no
load applied.
4. Place the
MPEC Control Switch
(Figure 56) to the
OFF/RESET
position.
Figure 56. MPEC Control Switch (Off/Reset)
5. Verify that the
all
status LED on the MPEC display
are
OFF
(not lit).
6. Remove all loads from the generator.
Emergency Shutdown Procedure
1. To shut-down the engine in the event of an emergency,
switch the
MAIN
,
GFCI
and
LOAD
(Figure 39) circuit
breakers to
OFF
position.
2. Place the
MPEC Control Switch
switch (Figure 56) to
the
OFF/RESET
position.
NEVER
stop the engine suddenly except in an emergency.
DO NOT
use the emergency stop switch a as method of
shutting down the generator. This switch is
ONLY
to be
used in the event of an emergency.
WARNING - SHUTTING DOWN THE GENERATOR
1. Perform steps 1 through 5 in the
Before Starting
section
as outlined in the
Manual Starting
Procedure
.
2. Place the
MPEC Control Switch
(Figure 55) in the
AUTO
position .
3. Continue to follow the steps outlined in the
Manual Start-
up
procedure (start at step 9).
Figure 55. MPEC Control Switch (AUTO)
When the generator is set in the
AUTO
mode, the generator will
automically start
in the event of
comercial power falling below a
prescribed level by means of a
contact closure that is generated
automatically by a transfer switch.
NOTE
Starting (Auto Mode)
Before connecting this generator to any
building’s electrical system, a
licensed
electrician
must install an
isolation
(transfer)
switch
. Serious damage to the
building’s electrical system may occur
without this transfer switch.
DANGER - ELECTRICAL SYSTEM HAZARDS
When connecting the generator to a isolation (transfer)
switch,
ALWAYS
have power applied to the generator's
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
CAUTION - BACKUP GENERATOR USE
When running the generator in the
AUTO
mode, remember
the generator can start up at any time without warning.
NEVER
attempt to perform any maintenance when the
generator is in the auto mode.
WARNING - AUTO MODE MAINTENANCE
19. The generator will run until manually stopped or an
abnormal condition occurs.
DCA-70USI (60 Hz) — GENERATOR START-UP PROCEDURE (AUTO MODE)
When the
MPEC
Control Switch
is placed in the
AUTO
position,
the engine glow plugs will be
warmed and the engine will start
automatically. The pre-heat lamp
will turn off when the engine has
started.
NOTE
Содержание MQ POWER WhisperWatt DCA70USI
Страница 2: ...PAGE 2 DCA 70USI 60 Hz OPERATION AND PARTS MANUAL REV 0 01 04 06 ...
Страница 20: ...PAGE 20 DCA 70USI 60 Hz OPERATION AND PARTS MANUAL REV 0 01 04 06 NOTE PAGE ...
Страница 47: ...DCA 70USI 60 Hz OPERATION AND PARTS MANUAL REV 0 01 04 06 PAGE 47 1 NOTE PAGE ...
Страница 66: ...PAGE 66 DCA 70USI 60 Hz OPERATION AND PARTS MANUAL REV 0 01 04 06 DCA 70USI 60 Hz BATTERY ASSY BATTERY ASSY ...
Страница 68: ...PAGE 68 DCA 70USI 60 Hz OPERATION AND PARTS MANUAL REV 0 01 04 06 DCA 70USI 60 Hz MUFFLER ASSY MUFFLER ASSY ...
Страница 70: ...PAGE 70 DCA 70USI 60 Hz OPERATION AND PARTS MANUAL REV 0 01 04 06 DCA 70USI 60 Hz FUELTANK ASSY FUEL TANK ASSY ...
Страница 83: ...DCA 70USI 60 Hz OPERATION AND PARTS MANUAL REV 0 01 04 06 PAGE 83 1 NOTE PAGE ...