14
—
Relay Contact
Two relay outputs with current carrying capacity of
1A @ 24 VDC
DIP Switches
Master, Coupler, Turbo Ring, Reserve
Digital Input
Two inputs with the same ground, but electrically
isolated from the electronics
• For state “1”: +13 to +30V
• For state “0”: -30 to +3V
• Max. input current: 8 mA
Optical Fiber
Multi-mode
Single-mode
Single-mode,
80 km
Wavelength
1300 nm
1310 nm
1550 nm
Max. Tx
-10 dBm
0 dBm
0 dBm
Min. Tx
-20 dBm
-5 dBm
-5 dBm
Rx Sensitivity
-32 dBm
-34 dBm
-34 dBm
Link Budget
12 dB
29 dB
29 dB
Typical Distance
5 km (a)
4 km (b)
40 km (c)
80 km (d)
Saturation
-6 dBm
-3 dBm
-3 dBm
a. using [50/125
μ
m, 800 MHz*km] cable
b. using [62.5/125
μ
m, 500 MHz*km] cable
c. using [9/125
μ
m, 3.5 PS/(nm*km)] cable
d. using [9/125
μ
m, 19 PS/(nm*km)] cable
Power
Input Voltage
12 to 45 VDC, redundant inputs
Input Current (@24V) Max. 0.24A: (EDS-505A)
Max. 0.26A: (EDS-508A)
Max. 0.35A: (EDS-505A-MM, EDS-505A-SS)
Max. 0.36A: (EDS-508A-MM, EDS-508A-SS)
Connection
Two removable 6-pin terminal blocks
Overload Current
Protection
Present
Reverse Polarity
Protection
Present
Mechanical
Casing
IP30 protection, metal case
Dimensions
80.5
×
135
×
105 mm (W
×
H
×
D)
Weight
1.04 kg
Installation
DIN-Rail, Wall Mounting (optional kit)
Environment
Operating Temperature 0 to 60°C (32 to 140°F),
-40 to 75°C (-40 to 167°F ) for -T models
Storage Temperature
-40 to 85°C (-40 to 185°F)
Ambient Relative
Humidity
5 to 95% (non-condensing)
Regulatory Approvals
Safety
UL60950-1, UL 508, CSA C22.2 No. 60950-1,
EN60950-1