EDS-405 User’s Manual
Dip Switch Settings
EDS-405 Series Dip Switches
6
1
2
3
4
5
RM
P1
P2
P3
P4
P5
Set to ON:
P1-P5
(Default is Off)
Enables the corresponding PORT Alarm. If the port’s link fails, the
relay will form an open circuit and the fault LED will light up.
RM
(Default is Off)
Enables this EDS-405 to be the Ring Master in a Turbo Ring
topology, and enable the Turbo Ring break alarm. If the EDS-405
is the Master of this Turbo Ring, and the Turbo Ring is broken, the
relay will form an open circuit.
Set to Off:
P1-P5
Disables the corresponding PORT Alarm. The relay will form a
closed circuit and the Fault LED will never light up.
RM
Disables this EDS-405 from being the Ring Master in a Turbo Ring
topology, and disables the Turbo Ring break alarm. If the EDS-405
is the Master of this Turbo Ring, and the Turbo Ring is broken, the
relay will form a closed circuit.