Motrona touchMATRIX MX350 Скачать руководство пользователя страница 40

Mx350_01a_oi_e.docx / Nov-19 

 

 

page 40 / 72 

Continuation „PRESELECTION 1 MENU“: 
 

MODE 1 

Switching conditions for preselection 1. Output/ relay/ display switches under the following conditions:

 

 

0  |RESULT|>=|PRES| 

Absolute value of the display value is greater or equal absolute value of 
PRESELECTION 1 
With HYSTERESIS 1 not equal 0 the following switching condition is applied: 
Display value >= PRESELECTION 1 

 ON,  

Display value < PRESELECTION 1 – HYSTERESIS 1 

OFF 

1  |RESULT|<=|PRES| 

Absolute value of the display value is less or equal absolute value of 
PRESELECTION 1 (start-up suppression (START UP DELAY) is advisable) 
With HYSTERESIS 1 not equal 0 the following switching condition is applied: 
Display value <= PRESELECTION 1 

 ON,  

Display value > PRESELECTION 1 + HYSTERESIS 1 

OFF 

2  |RESULT|=|PRES| 

Absolute value of the display value is equal absolute value of PRESELECTION 1 
A range (Presel/- ½ Hysteresis) can be defined and monitored in 
conjunction with the hysteresis. 
With HYSTERESIS 1 not equal 0 the following switching condition is applied: 
Display value > PRESELECTION 1 + ½ HYSTERESIS 1 

 OFF,  

Display value < PRESELECTION 1 - ½ HYSTERESIS 1 

 OFF 

3  RESULT>=PRES 

Display value is greater or equal PRESELECTION 1, e.g. overspeed 
With HYSTERESIS 1 not equal 0 the following switching condition is applied: 
Display value >= PRESELECTION 1 

 ON,  

Display value < PRESELECTION 1 – HYSTERESIS 1 

OFF 

4  RESULT<=PRES 

Display value is less or equal PRESELECTION 1, e.g. underspeed 
(start-up suppression “START UP DELAY” is recommend) 
With HYSTERESIS 1 not equal 0 the following switching condition is applied: 
Display value <= PRESELECTION 1 

 ON,  

Display value > PRESELECTION 1 + HYSTERESIS 1 

OFF 

5  RESULT=PRES 

Display value is equal PRESELECTION 1. A range (Presel/- ½ Hysteresis) 
can be defined and monitored in conjunction with the hysteresis. 
With HYSTERESIS 1 not equal 0 the following switching condition is applied: 
Display value > PRESELECTION 1 + ½ HYSTERESIS 1 

 OFF,  

Display value < PRESELECTION 1 - ½ HYSTERESIS 1 

 OFF 

6  RESULT=0 

Display value is zero (Standstill after STANDSTILL TIME(s)), 
e. g. standstill monitoring (only for reference source SPEED A and SPEED B). 

7  RESULT>= PRES->0 

Auto reset to zero: (only for reference sources: COUNTER A, SECOND COUNTER A, 
COUNTER B and SECOND COUNTER B) 
Display value is greater or equal PRESELECTION 1, the display value is set to zero. 
If the BATCH MODE A or B is active, the corresponding batch counter increments 
or decrements when the display value is set to zero and when the corresponding 
reference source COUNTER A or COUNTER B was selected. 

8  RESULT<= 0->SET 

Auto set to PRESELECTION 1: (only for reference sources: COUNTER A, SECOND 
COUNTER A, COUNTER B and SECOND COUNTER B) 
Display value is less or equal zero, the display value is set to PRESELECTION 1. 
If the BATCH MODE A or B is active, the corresponding batch counter increments 
or decrements when PRESELECTION 1 is set and when the corresponding 
reference source COUNTER A or COUNTER B was selected. 

9  RES>=PRES-TRAIL 

Trailing

 

PRESELECTION 1: 

Display value is greater or equal PRESELECTION 2 – PRESELECTION 1 

 ON, 

PRESELECTION 1 is the trailing value from PRESELECTION 2 

 

Содержание touchMATRIX MX350

Страница 1: ...ontrast display with event controlled color variations Emulation of a 7 segment display inclusively icons and units Intuitive and easy parameterization by plain text and touchscreen 5 24 V auxiliary o...

Страница 2: ...df La description en fran ais est disponible sur https www motrona com fileadmin files bedienungsanleitungen Mx350_f pdf Version Description MX350_01a_oi mbo Nov 19 First Version Legal notices All con...

Страница 3: ...ntrol Output AO AR CO CR 13 AC Power supply Option AC 14 Relay Output Option RL 14 Display and touch screen 15 Screen structure for parametrization 15 Screen structure in operation 16 Error messages 1...

Страница 4: ...Mx350_01a_oi_e docx Nov 19 page 4 72 Diagnostics 62 Parameter serial codes 62 Linearization 68 Dimensions 70 Technical specifications 71...

Страница 5: ...rves the right to modify the hardware software or operation manual at any time and without prior notice Therefore there might be minor differences between the unit and the descriptions in operation ma...

Страница 6: ...cross sections for wiring are described in the Technical Specifications Before first start up it must be ensured that all connections and wires are firmly seated and secured in the screw terminals Al...

Страница 7: ...on as frequency display for incremental input signals Measurement of frequency RMP indicator Tachometers speed indicator Monitoring functions for speed and standstill Possibility of linking A B B A of...

Страница 8: ...Mx350_01a_oi_e docx Nov 19 page 8 72 Function diagram...

Страница 9: ...l GND terminals are internally interconnected Auxiliary Voltage Output Terminal 3 and 4 provide an auxiliary output for supply of sensors and encoders The output voltage depends on the power supply DC...

Страница 10: ...PNP NPN Namur Tri State Unconnected PNP inputs are always LOW and unconnected NPN inputs are always HIGH All inputs are designed to receive impulses from electrical impulse sources Notice for mechani...

Страница 11: ...2 signals The characteristics of the incremental input can be set in the GENERAL MENU Wiring of the incremental inputs RS422 HTL DIFFERENTIAL HTL PNP single ended HTL NPN single ended Unconnected PNP...

Страница 12: ...ng contacts When exceptionally mechanical contacts are used please connect an external capacitor between GND and the corresponding input A capacity of 10 F will reduce the input frequency to 20 Hz and...

Страница 13: ...shows the connection to a PC by using a standard Sub D 9 connector Connection of the RS232 interface Connection of the RS485 interface Control Output AO AR CO CR Four control outputs are available at...

Страница 14: ...age output Devices with option AC can also be supplied with a DC voltage between 18 and 30 VDC at terminals 1 and 2 Relay Output Option RL Two relay outputs with potential free changeover contacts are...

Страница 15: ...ect the parameter menu via arrow buttons and confirm with OK The menu selection can be terminated with C Parameter selection Select the parameter via arrow buttons and confirm with OK The parameter se...

Страница 16: ...he touch screen Control or Relay status are only shown with option AO AR CO CR or RL Large Display 4 digits To switch to the next display press the top of the screen This is only possible with activat...

Страница 17: ...sel can be set in the display menu via the parameter QUICKSTART BUTTON To switch to the next display press the top of the screen or the skip button This is only possible with option AO AR CO CR or RL...

Страница 18: ...display is outside the displayable display range an error screen is briefly displayed every two seconds In this appears which display value was exceeded or fallen below The error messages described ar...

Страница 19: ...CTORY SETTINGS SPEED A SETTINGS DISPLAY VALUE BASE FREQUENCY DECIMAL POINT SAMPLING TIME WAIT TIME STANDSTILL TIME AVERAGE FILTER SCALE UNITS SPEED B SETTINGS DISPLAY VALUE BASE FREQUENCY DECIMAL POIN...

Страница 20: ...ART UP DELAY 3 EVENT COLOR 3 PRESELECTION 4 MENU SOURCE 4 MODE 4 HYSTERESIS 4 PULSE TIME 4 OUTPUT TARGET 4 OUTPUT POLARITY 4 OUTPUT LOCK 4 START UP DELAY 4 EVENT COLOR 4 Menu Parameter SERIAL MENU UNI...

Страница 21: ...x1 ENCODER PROPERTIES for MX350 This parameter determines the characteristics of the pulse input for MX350 0 PNP PNP switch to 1 NPN NPN switch to 2 NAMUR Connect sensor to GND and sensor to input A o...

Страница 22: ...ection values Master PIN 6079 This Lock function is only useful in conjunction with active lock function in PIN PARAMETER 0000 No lock 9999 Access after entering PIN Code 9999 PIN PARAMETER This param...

Страница 23: ...ighest value DECIMAL POINT This value defines the position of the decimal point 0 NO No decimal point 1 0000000 0 Decimal point at the specified position 2 000000 00 Decimal point at the specified pos...

Страница 24: ...ection can be set in PRESELECT MENU 0 00 Shortest time 99 99 Largest time AVERAGE FILTER Selectable average or filter function to avoid measuring fluctuations by unstable frequencies At setting 1 to 4...

Страница 25: ...inch 15 feet 16 Stueck 17 pcs 18 sec 19 min 20 Min Sec 21 H M S 22 Min Sec 00 23 l min 24 gal min 25 ml min 26 gr min 27 inch min 28 H M 29 Edit Unit A customized unit with up to 16 digits can be edit...

Страница 26: ...st value DECIMAL POINT This value defines the position of the decimal point 0 NO No decimal point 1 0000000 0 Decimal point at the specified position 2 000000 00 Decimal point at the specified positio...

Страница 27: ...ection can be set in PRESELECT MENU 0 00 Shortest time 99 99 Largest time AVERAGE FILTER Selectable average or filter function to avoid measuring fluctuations by unstable frequencies At setting 1 to 4...

Страница 28: ...ITS display unit of measurement This parameter determines which unit is shown on the display Setting the SCALE UNITS does not affect the display value The decimal point is set in the parameter DECIMAL...

Страница 29: ...l Inputs or PC user interface the counter of channel A is set to the value entered here 99999999 Smallest value 0 Default value 99999999 Highest value DECIMAL POINT This value defines the position of...

Страница 30: ...inch 15 feet 16 Stueck 17 pcs 18 sec 19 min 20 Min Sec 21 H M S 22 Min Sec 00 23 l min 24 gal min 25 ml min 26 gr min 27 inch min 28 H M 29 Edit Unit A customized unit with up to 16 digits can be edi...

Страница 31: ...counts here parallel to the main counter e g If the total counter should automatically reset to 0 when 4000 is reached the preset value e g PRESELECTION 3 must be set to 4000 the reference source SOU...

Страница 32: ...rement This parameter determines which unit is shown on the display Setting the SCALE UNITS does not affect the display value The decimal point is set in the parameter SECOND DECIMAL POINT A list of p...

Страница 33: ...e entered here 99999999 Smallest value 0 Default value 99999999 Highest value DECIMAL POINT This value defines the position of the decimal point 0 NO No decimal point 1 0000000 0 Decimal point at the...

Страница 34: ...counts here parallel to the main counter e g If the total counter should automatically reset to 0 when 4000 is reached the preset value e g PRESELECTION 3 must be set to 4000 the reference source SOU...

Страница 35: ...parameter determines which unit is shown on the display Setting the SCALE UNITS does not affect the display value The number of decimal places must be defined with the parameter SECOND DECIMAL POINT...

Страница 36: ...display unit of measurement This parameter determines which unit is shown on the display Setting the SCALE UNITS does not affect the display value The decimal point is set in the parameter DECIMAL POI...

Страница 37: ...ctivated 3 SPEED B Result of frequency measurement on channel B Only visible if corresponding Operational Mode has been activated 4 COUNTER B Result of the counter on channel B Only visible if corresp...

Страница 38: ...CR AO AR or RL PRESELECTION 1 Preselection switching point 1 99999999 Smallest value 1000 Default value 99999999 Highest value PRESELECTION 2 Preselection switching point 2 99999999 Smallest value 20...

Страница 39: ...counter on channel A or A B 90 Only visible if Second Mode A has been activated 3 SPEED B Result of frequency measurement on channel B Only visible if corresponding Operational Mode has been activated...

Страница 40: ...START UP DELAY is recommend With HYSTERESIS 1 not equal 0 the following switching condition is applied Display value PRESELECTION 1 ON Display value PRESELECTION 1 HYSTERESIS 1 OFF 5 RESULT PRES Displ...

Страница 41: ...tching condition of preselection 1 0 000 No output pulse static signal 60 000 Pulse duration of 60 seconds OUTPUT TARGET 1 Assignment of an output or relay for the switching condition of preselection...

Страница 42: ...PEED B Start Up Delay 3 and 4 have an automatic start up suppression 00 000 No start up suppression 60 000 Start up suppression in seconds EVENT COLOR 1 Event depending change of the display color for...

Страница 43: ...N 1 MENU PULSE TIME 2 S Duration of output pulse for the switching condition of preselection 2 See chapter PRESELECTION 1 MENU OUTPUT TARGET 2 Assignment of an output or relay for the switching condit...

Страница 44: ...3 See chapter PRESELECTION 1 MENU OUTPUT TARGET 3 Assignment of an output or relay for the switching condition of preselection 3 See chapter PRESELECTION 1 MENU OUTPUT POLARITY 3 Polarity for the swi...

Страница 45: ...TION 1 MENU OUTPUT TARGET 4 Assignment of an output or relay for the switching condition of preselection 4 See chapter PRESELECTION 1 MENU OUTPUT POLARITY 4 Polarity for the switching condition of pre...

Страница 46: ...e bit data format 0 7 EVEN 1 7 data Parity even 1 Stop 1 7 EVEN 2 7 data Parity even 2 Stops 2 7 ODD 1 7 data Parity odd 1 Stop 3 7 ODD 2 7 data Parity odd 2 Stops 4 7 NONE 1 7 data no Parity 1 Stop 5...

Страница 47: ...on is stopped for 20 s 0 000 All cyclic transmission is switched off The unit will send data upon a serial request or with command SERIAL PRINT 60 000 Cycle time in seconds SERIAL VALUE This parameter...

Страница 48: ...ult of the linked frequency of channel A and B A B A B B A Only visible if corresponding Operational Mode has been activated COUNTER COLL Result of the linked counters of channel A and B A B A B B A O...

Страница 49: ...or 20 4 mA when the ANALOG END value is reached e g 95 00 corresponds to a conversion of 9 5 V or 18 mA when the ANALOG END value is reached 0 Smallest gain 100 Default value 110 Highest gain ANALOG O...

Страница 50: ...DATA N A 16 TESTPROGRAM N A 17 SET RED COLOR The display lights up red The color can be changed by the event dependent color switching in the PRESELECTION 1 4 d 18 SET GREEN COLOR The display lights...

Страница 51: ...rther pulses as long as this command is present s 31 LOCK COUNTER B Counter channel B is disabled and stops counting any further pulses as long as this command is present s s static switching level ev...

Страница 52: ...DGE Activate at falling edge INPUT 2 ACTION This parameter defines the function of the input Ctrl In 2 See parameter INPUT 1 ACTION INPUT 2 CONFIG This parameter defines the switching characteristics...

Страница 53: ...1 COUNTER A Result of the counter on channel A or A B 90 2 SECOND COUNTER A Result of the second counter total counter batch counter on channel A or A B 90 Only visible if Second Mode A has been activ...

Страница 54: ...Only visible if corresponding Operational Mode has been activated 8 SCALED RESULT Result of the additionally scaled process value SOURCE DUAL DOWN Reference source for two line display second line 0...

Страница 55: ...y color by a switching condition is possible see PRESELECTION 1 4 MENU Event depending changes are only available for devices with option CO CR AO AR or RL 0 RED Red display 1 GREEN Green display 2 YE...

Страница 56: ...O AR RL 0 EDIT PRESEL Editing menu is opened after pressing the left command key and Preselection Values can be changed Attention Monitoring of the switching outputs correction of the analogue output...

Страница 57: ...onal Mode has been activated 5 SECOND COUNTER B Result of the second counter total counter batch counter on channel B or A B 90 Only visible if Second Mode B has been activated 6 FREQUENCY COLL Result...

Страница 58: ...the following request string to the converter EOT AD1 AD2 C1 C2 ENQ EOT control character Hex 04 AD1 unit address High Byte AD2 unit address Low Byte C1 register code High Byte C2 register code Low B...

Страница 59: ...ter setting Required parameter settings in MX350 MX355 Serial menu UNIT NUMMER Not valid for Modbus communication For setting of Modbus address see parameter MODBUS SERIAL BAUD RATE This parameter def...

Страница 60: ...l variables actual data and status registers are mapped to Modbus Holding Registers However as all registers of the device are 32 bit registers but Modbus Holding registers are only 16 bit registers e...

Страница 61: ...set single commands Coil number Serial code of command Command 0 54 Reset Set Reset Set Value of channel A and B 1 55 Freeze Display Freeze actual display value 2 56 Touch Disable Disable touch screen...

Страница 62: ...6 SPEED A SETTINGS AVERAGE FILTER 16 0 0 8 17 SPEED A SETTINGS SCALE UNITS 17 0 0 29 18 SPEED A SETTINGS __ 18 0 0 0 19 SPEED A SETTINGS __ 19 0 0 0 20 SPEED A SETTINGS __ 20 0 0 0 21 SPEED B SETTINGS...

Страница 63: ...ECTION VALUES PRESELECTION 1 B1 1000 99999999 99999999 61 PRESELECTION VALUES PRESELECTION 2 B2 2000 99999999 99999999 62 PRESELECTION VALUES PRESELECTION 3 B3 3000 99999999 99999999 63 PRESELECTION V...

Страница 64: ...2 0 0 1 102 PRESELECTION 4 MENU EVENT COLOR 4 F3 0 0 3 103 PRESELECTION 4 MENU __ F4 0 0 0 104 SERIAL MENU UNIT NUMBER 90 11 11 99 105 SERIAL MENU SERIAL BAUD RATE 91 0 0 2 106 SERIAL MENU SERIAL FORM...

Страница 65: ...99999999 99999999 0 153 LINEARIZATION MENU P5 Y K0 99999999 99999999 0 154 LINEARIZATION MENU P6 X K1 99999999 99999999 0 155 LINEARIZATION MENU P6 Y K2 99999999 99999999 0 156 LINEARIZATION MENU P7...

Страница 66: ...LINEARIZATION MENU P19 Y M8 99999999 99999999 0 182 LINEARIZATION MENU P20 X M9 99999999 99999999 0 183 LINEARIZATION MENU P20 Y N0 99999999 99999999 0 184 LINEARIZATION MENU P21 X N1 99999999 999999...

Страница 67: ...e Command 54 RESET SET 55 FREEZE DISPLAY 56 TOUCH DISABLE 57 CLR LOCK 58 CLR MIN MAX 59 SERIAL PRINT 60 TEACH PRES 1 61 TEACH PRES 2 62 TEACH PRES 3 63 TEACH PRES 4 64 SCROLL_DISPLAY 65 CLEAR LOOP TIM...

Страница 68: ...parameters P1 X to P24 X are used to specify the coordinates on the x axis These are the measuring values that the unit normally would generate according to the actual input signal Now enter the attac...

Страница 69: ...ion Example The picture below shows a watergate where the opening is picked up by means of an incremental encoder We would like to display the clearance of the gate d but the existing encoder informat...

Страница 70: ...Mx350_01a_oi_e docx Nov 19 page 70 72 Dimensions...

Страница 71: ...50 mA Incremental inputs Number of inputs Configuration Format Frequency Load 2 A B PNP NPN Namur or Tri State HTL Low 0 3 V High 9 30 V max 250 kHz max 6 mA Ri 5 kOhm 470 pF Incremental inputs MX355...

Страница 72: ...e Digit height Color Operation Graphic LCD with backlight 8 digits plus sign 99999999 99999999 13 mm height red green yellow selectable resistive touchscreen Housing Material Mounting Dimensions w x h...

Отзывы: