background image

Pu202_02d_oi_e.doc / Apr-16 

 

Page 9 / 10 

7.

 

Output Signal 

The quadrature output operates with a phase displacement between signals A/A’ and B/B’. 

 

In case of a quadrature type input signal with 90° phase shifting according t

6.1

the output 

appears with the same displacement of 90°. However, with inputs according t

6.2

 and 

6.3

, the 

phase displacement at the output will be constant in time, therefore will correspond to 90° only 
at a certain input frequency and will become smaller with lower input frequencies. 

 

This in general, this is not a restriction for proper detection of the direction, because most of 
the controllers can clearly interpret this information, even when the phase is barely visible on 
an oscilloscope. 

 

 

 

 

 
DIL switch slider S1 permits selection of 5 different times. The frequency is shown in brackets 
at which the phase displacement corresponds to 90°. 

 

 

1 2 3 4

ON

OFF

S1

0,4  µsec. (625kHz)

 

 

 

 

1 2 3 4

ON

OFF

S1

1,1  µsec. (227kHz)

 

 

 

 

1 2 3 4

ON

OFF

S1

   4  µsec. (62,5kHz)

 

 

 

 

1 2 3 4

ON

OFF

S1

 11  µsec. (22,7kHz)

 

 

 

 

1 2 3 4

ON

OFF

S1

 40  µsec. (6,25kHz)

 

 

Содержание PU202

Страница 1: ...al separation Product features Converts HTL signals from 10 up to 30 V A B Z into the corresponding TTL RS422 format the inverted channels included Further different standards of direction signals can...

Страница 2: ...eproduction modification usage or publication in other electronic and printed media as well as in the internet requires prior written authorization by motrona GmbH Table of Contents 1 Safety Instructi...

Страница 3: ...e right to modify the hardware software or operation manual at any time and without prior notice Therefore there might be minor differences between the unit and the descriptions in operation manual Th...

Страница 4: ...sections for wiring are described in the Technical Specifications see chapter 8 Before first start up it must be ensured that all connections and wires are firmly seated and secured in the screw term...

Страница 5: ...ontrollers Some measuring systems or PLC positioning cards generate pulses on one line whilst another line provides static information of the direction of rotation Other systems use two separate lines...

Страница 6: ...unit is designed as a PCB with a plastic housing for a simple snapping ontotop hat rails according to the EN 60715 norm The impulse input are available on a 9 pin SUB D connector female For power supp...

Страница 7: ...inal Also Pin 4 of the input connector is on same potential as the 24V screw terminal This enables the user to externally supply an encoder system via the Sub D connector without necessity to split th...

Страница 8: ...converted to TTL level but not be affected by the mode setting ON 6 1 Quadrature Input A B 2 x 90 1 2 3 4 5 6 7 8 ON OFF S2 6 2 Impulses on line A only static direction select on line B Low forward Hi...

Страница 9: ...90 only at a certain input frequency and will become smaller with lower input frequencies This in general this is not a restriction for proper detection of the direction because most of the controller...

Страница 10: ...Frequency Connections HTL 10 30 V PNP Ri 10 kOhm A B Z max 200 kHz male SUB D connector 9 pin Incremental output Levels Channels Output current Signal delay Connections 5 V TTL RS422 A A B B Z Z max...

Отзывы: