DZ27001a_e.doc / Jan-13
Page 21 / 36
6.2.7.
Analogue-Menu
Analogue-Menu
(settings for analogue outputs)
Code Setting Range Default
Analogue Format
Output format of the analogue output
„E6“
0..3
0
0
Range -10V to +10V
1
Range 0V to +10V
2
Range 4mA to 20mA
3
Range 0mA to 20mA
Analogue Start
Start value (engineering units) for 0V or -10V or 0mA or 4mA
„E7“
-10000000
..10000000
0
Analogue End
End value (engineering units) for 10V or 20mA
„E8“
-10000000
..10000000
10000
Analogue Swing
Max. output value (100 = 10V or 20mA)
„E9“
0..1000
100
Analogue Offset
Shift of the zero position (mV)
„F0“
-9999..9999
0
The settings above are at the same time used to generate the Basic Value 0 - 10 000
(corresponding to 0 - 100,00 %), which finally can be read out from the serial register
with access code :8 (see 6.2.3)