6.2.9.
Switching –Menu
These parameters are not relevant for model DZ276.
Indications | f | mean that only the absolute value of the frequency is considered. With all
other indications, frequencies are categorically signed (+ with forward and - with reverse)
Switching -Menu
(Switching characteristics of relays/outputs)
Code Setting Range Default
Pulse Time 1
Rel.1: Duration of timed output, sec. (0=static)
„F8“
0 ... 9.99
0
Pulse Time 2
Rel.2: Duration of timed output, sec. (0=static)
„F9“
0 ... 9.99
0
Pulse Time 3
Rel.3: Duration of timed output, sec. (0=static)
„G0“
0 ... 9.99
0
Hysteresis 1
Rel.1: Switching Hysteresis (engineering units)
„G1“
0 ... 99999.9
0
Hysteresis 2
Rel.2: Switching Hysteresis (engineering units)
„G2“
0 ... 99999.9
0
Hysteresis 3
Rel.3: Switching Hysteresis (engineering units)
„G3“
0 ... 99999.9
0
Preselect Mode 1
(switching operation for relay 1/output 1)
„G4“
0..8
0
0
|f| >= |Preselection| (catch*)
1
|f| <= |Preselection| with start-up-delay (catch*)
2
|f| == |Preselection| with start-up-delay (catch*)
3
Standstill (f=0) after expiration of standstill time
4
f >= Preselection (catch*)
(also suitable for signalization of forward direction)
5
f <= Preselection (catch*)
(also suitable for signalization of reverse direction)
6
f == Preselection (catch*)
7
Relay/output signals "forward" when a positive frequency (f >
0) is detected. This information disappears upon detection of
"standstill"
8
Relay/output signals "reverse" when a negative frequency (f <
0) is detected. This information disappears upon detection of
"standstill"
Preselect Mode 2
(switching operation for relay 2/output 2)
see Preselection Mode 1
„G5“
0..8
0
Preselect Mode 3
(switching operation for relay 3/output 3)
see Preselection Mode 1
„G6“
0..8
0
Output Polarity
(Relay/output active „on“ or active „off“ **)
Parameter with binary interpretation
„G7“
0..7
0
0
all Relays are energized when the assigned event occurs
1
Relay 1/transistor output 1
inverted
2
Relay 2 transistor output 2
inverted
3
Relay 1&2 transistor output 1&2
inverted
4
Relay 3 transistor output 3
inverted
5
Relays 1&3 transistor output 1&3
inverted
6
Relays 2&3 transistor output 2&3
inverted
7
All relays
inverted
*)
The corresponding relay/output can be used with catch operation, when a catch function has been
assigned to it under parameter „Lock Relay“
**)
Active "on" means the relay/output will be energized upon occurrence of the assigned event
Active "off" means the relay/output will be de-energized upon occurrence of the assigned event