Fault Mode 

The 

VMX Series

 will automatically enter the Fault Mode when a fault occurs in the motor or starter and display 

a code indicating the condition that caused a shutdown. Fault codes are three-digits in length and are displayed 
in alpha characters. The first and second characters (reading left to right) are the initials for the applicable 
English-language fault name. The third or right-most character can be either A, c, or d to denote when the fault 
occurred. “A” denotes Acceleration. “c” denotes Constant speed. “d” denotes Decel.  

Fault History

 of the past 3 events is stored and can be accessed by using the Up or Down Arrow keys before 

pressing the Reset button. The first (newest) event is indicated by the decimal point in the lower right corner. A 
more detailed history with time and date stamps is also kept in Functions 85 through 93. 

Fault Codes: 

Basic common fault codes are shown in the chart below. For additional details refer to Chapter 7 of the 
Advanced Installation, Operation and Programming Manual, or contact the factory for assistance. 

 

Fault Condition Description 

Fault Display Code 

Readout 

Fault Number Code 

used in History, 

F085, F088 and 

F091 

LED 

Indicator 

Over Current

 during Accel; Const spd; Decel 

ocA; occ: ocd 

1; 2; 3 

Over Current  

Phase Loss

 during Accel; Const spd; Decel 

PLA; PLc; PLd 

4; 5; 6 

Phase Loss  

Over Temperature

 during Accel; Const spd; Decel 

otA; otc; otd 

7; 8; 9 

Over Temp  

Over Load 

during Accel; Const spd; Decel 

oLA; oLc; oLd 

10; 11; 12 

Over Load 

Shorted SCR

 during Accel; Const spd; Decel 

SSA; SSc; SSd 

13; 14; 15  

Shorted SCR 

Shunt Trip

 during Accel; Const spd; Decel 

st 

16; 17; 18 

Shunt Trip 

Current Imbalance

 during Accel; Const spd; Decel 

IBA; Ibc; IBd 

19; 20; 21 

--- 

Under Current 

during Accel; Const spd; Decel 

UcA; Ucc; Ucd 

22; 23; 24  

--- 

Short Circuit 

during Accel; Const spd; Decel 

ScA; Scc; Scd 

25; 26; 27 

Over Current 

Ground Fault

 during Accel; Const spd; Decel 

GFA; GFc; GFd 

28; 29; 30 

--- 

Bypass Discrepancy

 during Accel; Const spd; Decel 

BPA; BPc; BPd 

31; 32; 33 

--- 

PTC Trip

 during Accel; Const spd; Decel 

PtA; Ptc; Ptd 

34; 35; 36 

Over Load 

Rotation Trip

 during Accel; Const spd; Decel 

RtA; rtc; rtd 

37; 38; 39 

--- 

 

Additional codes that may be displayed 

Display Code 

Readout 

 Condition Description 

nFLA 

No Full Load Amps set in F001

 

Inh 

Inhibit: 

Starter is still Run mode when you are attempting a change in programming, or the starter 

has Password Protection enabled and you have not entered the password code. 

n3Ph No 

Phase: 

No input line voltages on one or more phases 

Loc 

Lockout: 

The unit has tripped on Overload and you are attempting to Reset before it is ready, 

or one of the Duty Cycle Lockout protection features has been enabled. 

Err

 

Error: 

You are attempting to enter an invalid password 

Table 7.1: Fault and Display code list 

 

 

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание VMX-1000-BP

Страница 1: ...or Control Document VMX QSG604132MN Firmware Revision 3 01 VMX Series Digital Solid State Soft Starter 18 1000A Basic Installation and Quick Startup Guide Phone 800 894 0412 Fax 888 723 4773 Web www c...

Страница 2: ...Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 1000A Page 2 of 27 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 3: ...ing and Inspection 8 SERVICE WARNING 8 Mounting Clearances and Cleaning 9 Power Connection and Terminations 10 Control Power Requirements 12 Control Connections 12 Chapter 3 Sequence of Operation Star...

Страница 4: ...Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 1000A Page 4 of 27 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 5: ...e been checked Power lines are attached to the unit input terminals marked L1 L2 and L3 R S T Motor leads are connected to the lower terminals marked T1 T2 and T3 U V W Appropriate control power is ap...

Страница 6: ...nd Ratings The Motortronics VMX Series starters are current rated controllers Max Amp ratings are for continuous duty and must not be exceeded Always check the motor nameplate FLA and Service Factor i...

Страница 7: ...38 VMX 210 BP through VMX 450 BP 17 11 15 15 11 23 11 00 0 40 VMX 550 BP CF CF CF CF CF CF VMX 718 BP through VMX 900 BP CF CF CF CF CF CF Panel open with integral bypass contactor VMX 1000 BP CF CF C...

Страница 8: ...Units without the BP Bypass Contactor optional on 210A and above must have ventilation adequate to account for heat dissipation of the SCRs This must be estimated at 4 5 watts per running load amp For...

Страница 9: ...it must be installed with its heat sink ribs oriented vertically and running parallel to the mounting surface Keep in mind that these are minimums Wiring may require more clearance particularly on the...

Страница 10: ...a load even for testing The VMX Series will trip on Phase Loss if any or all of the conductors are disconnected from the load terminals Contact the Factory for assistance in no load testing Caution Ne...

Страница 11: ...del Number Current Range Min Max Suggested Wire Size AWG Tightening Torque in lbs Screw Bolt Size Tightening Torque Nm Suggested Wire Size ISOmm2 VMX 18 BP 9 18 12 6 VMX 28 BP 14 28 10 10 VMX 39 BP 19...

Страница 12: ...be customer supplied unless an optional control power transformer see table below has been supplied with the unit Control Power Requirements When sizing a control power transformer for the VMX BP Ser...

Страница 13: ...3 When this contact is closed the VMX Series starter will start and run When it is opened it is the same as a Stop command Note When a maintained contact is used for start stop it is advisable to set...

Страница 14: ...cator on TB1 terminals 11 and 12 The output Triac switch is rated for 10 250 VAC DC 50 mA maximum If the three programmable Output Auxiliary Relays are being used for other functions this output can e...

Страница 15: ...ons See Section 8 for additional relay programming details Note It is not necessary to use the programmable output auxiliary relays in the Start Stop circuit An internal seal in relay is provided else...

Страница 16: ...period hit the Stop button immediately and open the disconnect line Stopping If Pump Flex Decel is Disabled factory default in F024 7 Remove the Run Command or hit the Stop button 8 At Speed LED will...

Страница 17: ...tep though large numbers Power On Control power is available at A1 and A2 Green LEDs At Speed The motor is at full power and the Bypass Contactor has been commanded to pull in The SCRs are at full con...

Страница 18: ...l function F001 should display with the selected digit flashing If the VMX Series starter has been programmed and power to the unit has not been cycled the readout will display the last function viewe...

Страница 19: ...Indicates you have increased the value to 24A the lowest setting for a 48A unit which is 1 2 of the Max Amps see Note Press the UP Arrow key twice 2 x to increase this digit value 0026 Indicates you...

Страница 20: ...mp 1 0 600 Motor Current 1 200 F013 Accel Ramp Time of Ramp 1 1 120 seconds 1 second 10 seconds F014 Max Current Limit of Ramp 1 200 600 Motor Current 1 350 F015 Initial Torque VR of Ramp 2 0 100 Line...

Страница 21: ...s 1 4 Phase Loss only F053 Auto Reset Attempts 0 Disabled or 1 10 attempts 1 0 F054 thru F059 Time and value displays for lockouts in F048 F050 Read only no settings F060 Aux Relay 1 setting Operation...

Страница 22: ...Trip Phase Rotation protection Phase rotation must match selection in Bit 2 below Setting to Off 0 will make the VMX insensitive for use behind a reversing contactor On Expected Phase Sequence 2 A B...

Страница 23: ...nges on Start resets on Stop 14 Ground Fault Trip 2 At Speed Stop 15 Phase Rotation Trip 3 At Speed End of Decel 16 Any Trip 5 15 4 Start End of Decel 17 Any Trip 5 15 flashing output 5 Short SCR Trip...

Страница 24: ...Over Current Phase Loss during Accel Const spd Decel PLA PLc PLd 4 5 6 Phase Loss Over Temperature during Accel Const spd Decel otA otc otd 7 8 9 Over Temp Over Load during Accel Const spd Decel oLA...

Страница 25: ...pping The Remaining Thermal Capacity can be viewed by using the UP or DOWN arrow keys when in the Status Display mode From the default Phase A Current screen dot on right side press the UP arrow key 4...

Страница 26: ...ble on the starter enclosure and or the driven equipment as required by local code NEMA Class Trip Curves NEMA Class trip curves are based on a common tripping point of 600 of motor Full Load Amps FLA...

Страница 27: ...the contactor No additional Overload Relay is necessary for normal operation Special Consideration for Across the Line Direct on Line Contactors When the Bypass Contactor on a VMX BP Series has been...

Отзывы: