![motortronics VMX-1000-BP Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/motortronics/vmx-1000-bp/vmx-1000-bp_installation-and-quick-start-manual_1839358023.webp)
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
Page 23 of 27
Aux. (Output) Relay Settings
Functions F060 through F062 provide the ability to program the functions of each of the 3 Output Auxiliary
Relays. Factory default programming is provided which covers a wide variety of applications, but any of these
relays can be changed as per the following chart.
Notes:
Check relay wiring before changing programming to avoid unintended consequences.
Relays programmed to some protection features will not operate if function is disabled elsewhere.
Setting
Relay Operation Description
Setting
Relay Operation Description
1
Run / Stop (Changes on Start, resets on Stop)
14
Ground Fault Trip
2
At Speed / Stop
15
Phase Rotation Trip
3
At Speed / End of Decel
16
Any Trip (#5 - #15)
4
Start / End of Decel
17
Any Trip, (#5-#15)
flashing output*
5
Short SCR Trip
18
Coast Down Time Lockout
6
Phase Loss Trip
19
Starts Per Hour Lockout
7
Shunt Trip
20
Time Between Starts Lockout
8
OL (Motor Thermal Overload) Trip
21
Any Lockout (#18-#20)
9
OT (Starter Thermal Over Temperature) Trip
22
Run Timer (F030) Engaged
10
Short Circuit Trip
23
Run / Stop with On-delay from F063
11
Current Unbalance Trip
24
At Speed / Stop with On-delay from F063
12
Over Current (Shear-Pin) Trip
25
At Speed / End of Decel w/ On-delay from F063
13
Under Current Trip
26
Start / End of Decel with On-delay from F063
*Note: Flash rate for Setting #17 is ½ second On and Off
Table 8: Aux. Relay Settings