Basic Installation and Operation Guide                VMX Series Digital Solid State Soft Starters   18 – 1000A 

 

Page 19 of 27 

Display

Press

Key...

Shows...

M eans...

Phase A
Current

Function #1
Selected

Default Setting
of Function #1

Lowest value
for this unit

Cursor (flashing)
Position Shift

New Value of
Second Digit

0000.

F001

0000

0024

0026

0036

 End

Value Accepted
(flashes once)

Return to
Function # Display

Figure 14:

Changing a Function Value

Example 1: Setting the Motor FLA

on a VMX-48 to 36A

F001

READ

ENTER

Fn

READ

ENTER

Lowest value
for this unit

0026

x 2

Returns to Default
Display, Phase A
Current

0000.

Fn

 

Example 1: Figure 14  

Entering a new FLA setting into Funtion 1 

 

[0000.]  

Indicates Phase A is drawing no current  
(unit is in Off mode). 

 

Press the [Fn] key 

[F001]  

Indicates this is Function 001 (Motor FLA).

 

Press [READ/ENTER] key 

to view the F001 value 

[0048] 

Indicates the programmed motor FLA is 0000 
Amps, the factory default for a new unit that has 
not yet been in service. The farthest left digit (0) 
is flashing, indicating that this is the digit that 
you will alter (cursor position).

 

Press the UP Arrow key once 

to increase this digit value 

[0024] 

Indicates you have increased the value to 24A, 
the lowest setting for a 48A unit, which is 1/2 of 
the Max. Amps (see Note)

Press the UP Arrow key twice (2 x) 

to increase this digit value 

[0026] 

Indicates you have increased the far left digit 
value from 4 to 6,

 

Press the LEFT Arrow key  

to shift left to the next digit 

[0026]  

The second digit from the left is now flashing, 
indicating a new cursor position. 

Press the UP Arrow key  

to increase this digit value 

[0036] 

Indicates you have increased the 2

nd

 to left digit 

to a value of 3 (10’s place), indicating a final 
setting value of 36A 

Press [READ/ENTER] key 

to store the new value 

[End] 

The word “

End

” will flash briefly to indicate that 

the new value has been entered and accepted. 
After flashing once, the display will revert to 
showing the Function number

 

 

Press the [Fn] key 

[0000.]  

Returns to the Default Display, indicating Phase 
A is drawing no current  
 

Note

:  

When first entering FLA into a new unit, pressing the Up arrow key will jump the readout value 
immediately to ½ of the unit Max. Amp rating, and it will never go below that again. Any unit 
thought to be new which has a value other than 0000 in F001 upon setup, has been programmed 
previously and should be reset to factory defaults before proceeding.

  

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание VMX-1000-BP

Страница 1: ...or Control Document VMX QSG604132MN Firmware Revision 3 01 VMX Series Digital Solid State Soft Starter 18 1000A Basic Installation and Quick Startup Guide Phone 800 894 0412 Fax 888 723 4773 Web www c...

Страница 2: ...Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 1000A Page 2 of 27 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 3: ...ing and Inspection 8 SERVICE WARNING 8 Mounting Clearances and Cleaning 9 Power Connection and Terminations 10 Control Power Requirements 12 Control Connections 12 Chapter 3 Sequence of Operation Star...

Страница 4: ...Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 1000A Page 4 of 27 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 5: ...e been checked Power lines are attached to the unit input terminals marked L1 L2 and L3 R S T Motor leads are connected to the lower terminals marked T1 T2 and T3 U V W Appropriate control power is ap...

Страница 6: ...nd Ratings The Motortronics VMX Series starters are current rated controllers Max Amp ratings are for continuous duty and must not be exceeded Always check the motor nameplate FLA and Service Factor i...

Страница 7: ...38 VMX 210 BP through VMX 450 BP 17 11 15 15 11 23 11 00 0 40 VMX 550 BP CF CF CF CF CF CF VMX 718 BP through VMX 900 BP CF CF CF CF CF CF Panel open with integral bypass contactor VMX 1000 BP CF CF C...

Страница 8: ...Units without the BP Bypass Contactor optional on 210A and above must have ventilation adequate to account for heat dissipation of the SCRs This must be estimated at 4 5 watts per running load amp For...

Страница 9: ...it must be installed with its heat sink ribs oriented vertically and running parallel to the mounting surface Keep in mind that these are minimums Wiring may require more clearance particularly on the...

Страница 10: ...a load even for testing The VMX Series will trip on Phase Loss if any or all of the conductors are disconnected from the load terminals Contact the Factory for assistance in no load testing Caution Ne...

Страница 11: ...del Number Current Range Min Max Suggested Wire Size AWG Tightening Torque in lbs Screw Bolt Size Tightening Torque Nm Suggested Wire Size ISOmm2 VMX 18 BP 9 18 12 6 VMX 28 BP 14 28 10 10 VMX 39 BP 19...

Страница 12: ...be customer supplied unless an optional control power transformer see table below has been supplied with the unit Control Power Requirements When sizing a control power transformer for the VMX BP Ser...

Страница 13: ...3 When this contact is closed the VMX Series starter will start and run When it is opened it is the same as a Stop command Note When a maintained contact is used for start stop it is advisable to set...

Страница 14: ...cator on TB1 terminals 11 and 12 The output Triac switch is rated for 10 250 VAC DC 50 mA maximum If the three programmable Output Auxiliary Relays are being used for other functions this output can e...

Страница 15: ...ons See Section 8 for additional relay programming details Note It is not necessary to use the programmable output auxiliary relays in the Start Stop circuit An internal seal in relay is provided else...

Страница 16: ...period hit the Stop button immediately and open the disconnect line Stopping If Pump Flex Decel is Disabled factory default in F024 7 Remove the Run Command or hit the Stop button 8 At Speed LED will...

Страница 17: ...tep though large numbers Power On Control power is available at A1 and A2 Green LEDs At Speed The motor is at full power and the Bypass Contactor has been commanded to pull in The SCRs are at full con...

Страница 18: ...l function F001 should display with the selected digit flashing If the VMX Series starter has been programmed and power to the unit has not been cycled the readout will display the last function viewe...

Страница 19: ...Indicates you have increased the value to 24A the lowest setting for a 48A unit which is 1 2 of the Max Amps see Note Press the UP Arrow key twice 2 x to increase this digit value 0026 Indicates you...

Страница 20: ...mp 1 0 600 Motor Current 1 200 F013 Accel Ramp Time of Ramp 1 1 120 seconds 1 second 10 seconds F014 Max Current Limit of Ramp 1 200 600 Motor Current 1 350 F015 Initial Torque VR of Ramp 2 0 100 Line...

Страница 21: ...s 1 4 Phase Loss only F053 Auto Reset Attempts 0 Disabled or 1 10 attempts 1 0 F054 thru F059 Time and value displays for lockouts in F048 F050 Read only no settings F060 Aux Relay 1 setting Operation...

Страница 22: ...Trip Phase Rotation protection Phase rotation must match selection in Bit 2 below Setting to Off 0 will make the VMX insensitive for use behind a reversing contactor On Expected Phase Sequence 2 A B...

Страница 23: ...nges on Start resets on Stop 14 Ground Fault Trip 2 At Speed Stop 15 Phase Rotation Trip 3 At Speed End of Decel 16 Any Trip 5 15 4 Start End of Decel 17 Any Trip 5 15 flashing output 5 Short SCR Trip...

Страница 24: ...Over Current Phase Loss during Accel Const spd Decel PLA PLc PLd 4 5 6 Phase Loss Over Temperature during Accel Const spd Decel otA otc otd 7 8 9 Over Temp Over Load during Accel Const spd Decel oLA...

Страница 25: ...pping The Remaining Thermal Capacity can be viewed by using the UP or DOWN arrow keys when in the Status Display mode From the default Phase A Current screen dot on right side press the UP arrow key 4...

Страница 26: ...ble on the starter enclosure and or the driven equipment as required by local code NEMA Class Trip Curves NEMA Class trip curves are based on a common tripping point of 600 of motor Full Load Amps FLA...

Страница 27: ...the contactor No additional Overload Relay is necessary for normal operation Special Consideration for Across the Line Direct on Line Contactors When the Bypass Contactor on a VMX BP Series has been...

Отзывы: