CPU Module
4-10
Pushbutton Functionality
The table below describes the use of the two pushbuttons in various scenarios, during power-
up and run-time. To press a pushbutton during startup, first press the pushbutton(s), then turn
on the RTU using the On/Off switch on the front panel. Keep the pushbutton(s) depressed for
the required number of seconds, as specified in the scenarios below.
Table 4-2 ACE3600 Pushbutton Functionality
Scenario
Trigger
Action
LEDs Test
During run-time, press PB1
for five or more consecutive
seconds (but less than 30).
All the LEDS on the CPU and I/O modules
will be lit until let go of PB1 and then
returned to their previous states.
RTU Restart
During run-time, press PB1
for 30 consecutive seconds.
All the LEDs will be lit. Then all the LEDs
will blink once.
The buzzer will buzz several short beeps.
(If PB1 is released during this time the
restart will not be performed.)
At the long beep, release PB1 and the RTU
will restart (and the buzzer will buzz.)
Turn LEDs ON
During run-time, press PB1
for one second.
Those LEDs which are currently active
will be turned on for a period of time
(configured in the RTU configuration
using the STS.)
RAM Test
During startup, press PB1.
A detailed memory test of SDRAM and
SRAM plug-in is performed.
- At the beginning of the RAM test, the
four indicator LEDs (see LEDs Location in
Table 4-3) will blink three times. During
the RAM test, the LEDs may blink or be
lit.
If the RAM test succeeds, the four LEDs
will blink three times and turn off and the
restart sequence will continue.
If the RAM test fails, the RTU will freeze
(restart sequence stops), the PWR LED
will blink and the four LEDs will blink
seven times. The failure error code will
then be displayed on the LEDs, in binary
code, as described in Table 4-3.
- To exit/abort the RAM test in the middle,
restart the RTU using the On/Off switch
on the front panel.
Содержание ACE3600 RTU
Страница 45: ...Installation 2 25 ...
Страница 46: ...Installation 2 26 Figure 2 28 19 Frame Metal Back Installation Combinations ...
Страница 100: ...Digital Input Module 6 7 Module Block Diagram 16 DI ...
Страница 101: ...Digital Input Module 6 8 32 DI ...
Страница 120: ...Digital Output Digital Input FET Module 8 6 Module Block Diagram 16 DO DI FET ...
Страница 121: ...Digital Output Digital Input FET Module 8 7 32 DO DI FET ...
Страница 125: ...Digital Output Digital Input FET Module 8 11 Specifications subject to change without notice ...
Страница 133: ...Digital Output Relay Module 9 8 Module Block Diagram 8 DO ...
Страница 134: ...Digital Output Relay Module 9 9 16 DO ...
Страница 155: ...Digital Output SBO Relay Module 11 9 Module Block Diagram 8 DO ...
Страница 156: ...Digital Output SBO Relay Module 11 10 16 DO ...
Страница 166: ...Analog Input Module 12 8 Module Block Diagram 8 AI ...
Страница 167: ...Analog Input Module 12 9 16 AI ...
Страница 178: ...Analog Output Module 13 8 Module Block Diagram 4 AO ...
Страница 186: ...Mixed I O Module 14 5 Module Block Diagram Mixed I O ...
Страница 193: ...Mixed Analog Module 15 4 Module Block Diagram Mixed Analog ...
Страница 342: ...OPTIMIZATION General No optimization is required for the ACE3600 units 25 1 ...
Страница 354: ...Break Fix Procedures Figure 29 3 Electrical Interconnection RTUs with I O slots 29 7 ...
Страница 355: ...Break Fix Procedures 29 8 Figure 29 4 Electrical Interconnection RTUs with no I O slots ...