Power Supply Module and Backup Battery
3-16
Motorola battery warranty is valid only when the battery is charged with the original
Motorola ACE3600 charging power supplies. Use of any other power supply/charger
will void the battery warranty.
Under various state or local laws, the batteries must be recycled or disposed of
properly and cannot be disposed of in landfills or incinerators. Environmental
protection regulations classify used Lead Acid batteries as hazardous waste, unless
certain exemptions apply. Consideration should be given to the methods of collecting,
labeling, handling and shipping used Lead Acid batteries. Please consult the
environmental protection authority for specific legal requirements and for recycling
options in your country/area.
Backup Battery Storage, Lifespan, Inspection and Replacement
The manufacturer’s recommendations for handling during each of the battery’s life stages are:
•
Transportation:
Batteries must be handled with care to prevent falls, impact, short circuit or exposure
to high temperatures and fire.
•
Battery Storage:
Storage of batteries in a warehouse requires a periodic recharge. The time between
these recharge cycles depends upon the storage temperature. The minimum open
circuit voltage allowed on the battery before recharging is 12.42 V, which represents
remaining capacity of approximately 30%. Therefore it is recommended to perform a
full charging cycle every few months depending upon the storage temperature of the
battery. Please refer to Table 3-1 to determine the suggested maximal period between
recharge cycles that suits the actual storage conditions. Improper storage may cause
deep discharge of the battery, which might cause degradation of the battery operating
life and lower the actual delivered capacity. Motorola performs a periodic full charge
cycle procedure on stored batteries and a final full charge operation prior to shipment.
•
Lifespan:
The average temperature of the battery environment affects the lifespan of batteries
installed in the field. Please refer to the battery vendor information at the following
website:
(Sonnenschein A512/6.5S and A512/10S): http://www.sonnenschein.org/A500.htm
•
Inspection and Replacement:
It is important to inspect the batteries periodically (recommended every 6-12 month)
and replace any battery that has corrosion on the leads or it is deformed or leaks. Such
a battery should be disposed according to the local environmental laws. To assure the
battery availability and proper operation, the battery should be replaced at the end of
its lifespan (approximately 30% capacity) even if it is still functional. Measure the
battery open circuit voltage using a digital voltmeter as described above. Please note
Содержание ACE3600 RTU
Страница 45: ...Installation 2 25 ...
Страница 46: ...Installation 2 26 Figure 2 28 19 Frame Metal Back Installation Combinations ...
Страница 100: ...Digital Input Module 6 7 Module Block Diagram 16 DI ...
Страница 101: ...Digital Input Module 6 8 32 DI ...
Страница 120: ...Digital Output Digital Input FET Module 8 6 Module Block Diagram 16 DO DI FET ...
Страница 121: ...Digital Output Digital Input FET Module 8 7 32 DO DI FET ...
Страница 125: ...Digital Output Digital Input FET Module 8 11 Specifications subject to change without notice ...
Страница 133: ...Digital Output Relay Module 9 8 Module Block Diagram 8 DO ...
Страница 134: ...Digital Output Relay Module 9 9 16 DO ...
Страница 155: ...Digital Output SBO Relay Module 11 9 Module Block Diagram 8 DO ...
Страница 156: ...Digital Output SBO Relay Module 11 10 16 DO ...
Страница 166: ...Analog Input Module 12 8 Module Block Diagram 8 AI ...
Страница 167: ...Analog Input Module 12 9 16 AI ...
Страница 178: ...Analog Output Module 13 8 Module Block Diagram 4 AO ...
Страница 186: ...Mixed I O Module 14 5 Module Block Diagram Mixed I O ...
Страница 193: ...Mixed Analog Module 15 4 Module Block Diagram Mixed Analog ...
Страница 342: ...OPTIMIZATION General No optimization is required for the ACE3600 units 25 1 ...
Страница 354: ...Break Fix Procedures Figure 29 3 Electrical Interconnection RTUs with I O slots 29 7 ...
Страница 355: ...Break Fix Procedures 29 8 Figure 29 4 Electrical Interconnection RTUs with no I O slots ...