MOTORSAVER
®
201A-AU SPECIFICATIONS
Functional Characteristics
Low Voltage
Trip
90% of setting
Reset
93% of setting
High Voltage
Trip
110% of setting
Reset
107% of setting
Voltage Unbalance
Trip
2-8%
Reset
Trip setting - 1% (5-8%)
Trip setting - 0.5% (2-4%)
Trip Delay
High/Low Voltage and Unbalance
1-30 seconds, adjustable
Single-Phasing
1 second, fixed
Restart Delay
1-500 seconds, adjustable; Manual
Input Characteristics
Line Supply Voltage
201A-AU
190-480VAC
201-575-AU
475-600VAC
Frequency
50/60Hz
Output Characteristics
Output Contact Rating
Pilot Duty
480VA @ 240VAC
General Purpose
10A @ 240VAC
General Characteristics
Environmental
Ambient Operating Temperature
-40
°
to 70
°
C (-40
°
to 158
°
F)
Relative Humidity
10-95%, non-condensing per IEC 68-2-3
Maximum Input Power
5 W
Standards Passed
Electrostatic Discharge (ESD)
IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency Immunity, Radiated
150 MHz, 10V/m
Fast Transient Burst
IEC 61000-4-4, Level 4, 4kV input power and controls
Surge Immunity
IEC
IEC 61000-4-5, Level 4, 4kV line-to-line; Level 4, 4kV
line-to-ground
ANSI/IEEE
C62.41 Surge and Ring Wave Compliance to a level of
6kV line-to-line
Hi-Potential Test
Meets UL508
(2 x rated V +1000 V for 1 minute)
Safety Marks
UL listed (OT08 octal socket required)
UL508 (File #E68520)
CE
IEC 60947-6-2
Dimensions
1.750” H x 2.375” W x 4.125” D (with socket)
Weight
9 oz.
Enclosure
Polycarbonate
Mounting Method
Plugs into OT08 Socket
Wire Gauge
12-22 AWG Solid or Stranded
Terminal Torque for P/N OT08 Socket
12 in. - lb
1
The ambient air temperature is the air temperature directly surrounding the product.
© 2010 SymCom, Inc. All Rights Reserved 9
Содержание 201-575-AU
Страница 10: ...2010 SymCom Inc All Rights Reserved 10 NOTES...
Страница 11: ...2010 SymCom Inc All Rights Reserved 11 NOTES...