OPERATION
After applying power
to the MotorSaver
®
, the
green RUN light will blink during the restart delay.
After
the restart delay time has expired, the
MotorSaver
®
will energize its output contacts (open the
normally closed and close the normally open contacts) and the RUN light will turn solid green.
Automatic Reset Mode
Set the RESTART (SEC) knob to the desired restart delay time. Apply 3-phase power to the motor.
The MotorSaver’s green RUN light will blink during the restart delay. Once the restart delay time has
expired, the MotorSaver® will energize its output contacts and the green RUN light will illuminate
.
Manual Reset Mode
Once power has been applied to the
MotorSaver®,
set the RESTART (SEC) knob to
M
to operate in
manual reset mode. When the MotorSaver
®
trips on a
fault, the red STATUS light will display the fault
code until the condition clears and the unit is reset by turning the RESTART (SEC) knob away from
the
M
position until the STATUS light turns green. The RESTART (SEC) knob can then be turned
back to the
M
position, requiring a manual reset after the next fault occurs. If power is lost before the
MotorSaver® is reset, the fault code will again be displayed once power is reapplied. This allows for
identification of the last fault even after power conditions have returned to normal
.
If the contacts do not energize and the RUN light does not turn solid green, see the
TROUBLESHOOTING section.
STATUS
INDICATOR LIGHT
GREEN RUN
GREEN
RESTART DELAY (Automatic Reset Mode)
GREEN
MANUAL RESET REQUIRED (Manual Reset Mode)
RED
REVERSE PHASE
RED
UNBALANCE / SINGLE PHASE
RED
HIGH VOLTAGE
RED LOW
VOLTAGE
Table 1: Diagnostic Indicator Lights
© 2010 SymCom, Inc. All Rights Reserved 6