background image

HIM

4

The Interface Solution Experts

Smart HART

 Loop

Interface and Monitor

Specifications

Input Accuracy:

 Reflects

the accuracy of the HART
field device

Input Impedance: 

Transmit

Mode: 150 ohms;
Receive Mode: Less than
5kohms

Input Over-Range
Protection: 

±5Vdc

ANALOG OUTPUTS
Output Accuracy:

 ±0.015%

of maximum output  span
(20mA).  Includes the
combined effects of linearity,
hysteresis, repeatability and
adjustment resolution.

Output Response Time:

<120ms, 10-90%

Isolation: 

500Vrms channel-

to-channel isolation;
1000Vrms between case,
input, outputs and power
terminals, and will withstand
1500Vac dielectric strength
test for one minute with no
breakdown

Ripple: 

Less than 10mV

peak-to-peak when
measured across a
250 ohm resistor

Output Limiting: 

130% of

span maximum; 125% of
span typical

Output Protection:

Transient protection on
output

Load Capability:

0-20mA, 1100 ohms
maximum

Load Effect: 

±0.01% of span

from 0 to maximum load
resistance

Line Voltage Effect:

±0.005% of output span for a
1% change in line voltage

Input Fail Modes: 

PC

programmable to fail high, fail
low, hold last, hold last then
fail high, or hold last then fail
low (configurable hold time, 0-
60 seconds)

Output Limits on Input
Failure: 

0-20mA:  Fail Low to

0mA or

 

Fail High to 23.6mA;

4-20mA:  Fail Low to 3.6mA
or Fail High to 23.6mA;
X-20mA (0<X<4):  Fail Low to
90% of XmA or Fail High to
23.6mA

Performance

Weight

Performance

(Continued)

Indicators

Indicators

(Continued)

Ambient

Conditions

+TX Power Supply: 

24.0Vdc

±10%@24mA

ALARM OUTPUTS
Digital Response Time:

Defined by HART protocol as
500msec maximum in Normal
HART Mode; 333msec
maximum in HART Burst
Mode

Alarm Response Time:

Digital Response Time +
150msec (Defined as time
from the field instrument’s
reporting a fault until the HIM
alarm is tripped)

Alarm Trip Delay:

Programmable from 0-120sec

MODBUS OUTPUTS
Type: 

Standard MODBUS

RTU protocol interface over
RS485 (parameters as
specified in U.S. Standard
EIA-RS485)

Address Range:

Configurable from 1 to 247.
Unit will assume a MODBUS
address of 01 by default

Baud Rate: 

Interface

supports the following:  300,
600, 1200, 4800, 9600, 19.2k.
MODBUS interface will
support even, odd and no
parities.  Unit will assume a
baud rate of 9600 and no
parity by default

Character Format: 

One start

bit, 8 data bits and one stop
bit

Data Format: 

User-

selectable Standard LSW
(Least Significant Word) or
Swapped MSW (Most
Significant Word).  Unit will
assume Standard LSW by
default

Power Consumption:

2-3.5W, nominal; 4.5W
@24Vdc maximum for units
using transmitter excitation to
supply loop power a 2-wire
instrument

LCD Type:

  Two-line LCD;

Top Row, 10mm (0.4 in) high
black digits on a reflective
background; Bottom Row,
6mm (0.225 in) high digits
on a reflective background;
two-digit HART address
indicator

Specifications and information subject to change without notice.

Format: 

Top row is five

alphanumeric characters,
plus sign and decimal point;
bottom row is five
alphanumeric characters

Decimal Points:

 User-

selectable for 0, 1, 2 or 3
places after the decimal point
or automatically adjusting with
a four decimal point maximum

Range: 

-99999 to 99999

Minimum Display Span:

1.00

Display Update Rate:

100msec

LED Type: 

 Dual color

red/green indicate:
INPUT LED:  Whether (green)
or not (red) the HART input is
connected and functioning
properly
READY LED:  Whether
(green) or not (red) the HIM is
initialized and operating
properly
TRIP 1 and 2 LED: Shows the
status of alarm off (green) or
alarm on (red)

Operating & Storage
Range:

-40°C to +85°C
(-40°F to +185°F)

Display Range:

-25°C to +85°C
(-13°F to +185°F)

Relay Range:

-25°C to +70°C
(-13°F to +158°F)

Relative Humidity:

0-95%, non-condensing

Ambient Temperature
Effect: 

 ±0.0065% of

span/°C maximum

RFI/EMI Immunity
(Standard):

20V/m@20-1000MHz, 1kHz
AM, when tested according to
IEC1000-4-3-1995

RFI/EMI Immunity (with
-RF Option): 

 30V/m@

20-1000MHz, 1kHz AM, when
tested according to IEC1000-
4-3-1995

Noise Rejection:

 Common

Mode: 100dB@50/60Hz

567 grams (16 ounces)

Содержание Smart HIM HART

Страница 1: ...HIM HIMNovember 2005 224 778 00C Smart HART Loop Interface and Monitor Smart HART Loop Interface and Monitor...

Страница 2: ...ions 5 Configuring the HIM 6 Installing the HIM 7 Installing the HIM into the Loop 7 Bench Checking the HIM 9 PC Configuration Software 10 HART Parameters 11 Display Parameters 13 Alarms Parameters 14...

Страница 3: ...hey have to offer Works with every Smart HART Device The instrument can be programmed in minutes to inter face with every HART compatible monitoring and con trol device About this Manual Wherever you...

Страница 4: ...interface over RS485 parameters as specified in U S Standard EIA RS485 Address Range Configurable from 1 to 247 Unit will assume a MODBUS address of 01 by default Baud Rate Interface supports the fol...

Страница 5: ...2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12 TX TX TX TX IN IN IN IN IN IN IN IN No Label I Source AO2 I Source AO2 A MODBUS 2 A MODBUS 2 ALARM RELAYS POWER NO1 CM1 NC1 I Source or I Sink AO2 I Source or I Sink...

Страница 6: ...re Once these software settings are made they are downloaded to the monitor in the form of a Configuration File and stored in the unit s non volatile memory You can choose to save a backup copy of the...

Страница 7: ...or 35mm Top Hat EN50022 DIN rails ElectricalConnections After mounting you are ready to connect the HIM to the loop Each unit comes equipped with a transmitter excitation terminal which allows it to s...

Страница 8: ...sted pair technique Shields are to be connected to an earth or safety ground at the unit itself The maximum length of unshielded input and output signal wiring should be 2 inches Power Sourcing Parame...

Страница 9: ...ut taking advantage of the Transmitter Excitation TX terminal If you need further descriptions of the terminals see Table 2 READY INPUT TRIP 2 TRIP 1 COM 0 ADDR For a HART Transmitter the resistor mus...

Страница 10: ...e device was configured HIM Tag A phrase used to identify a HIM Figure 7 HIM PC Configuration Software Screen HIM Device Status Displays how the HIM is function ing giving a brief summary of any error...

Страница 11: ...ny other HART device in the loop must be configured either as a HART Secondary Master 1 per loop or as a HART Slave up to 16 per loop Conversely setting the HIM to function as the Secondary HART Maste...

Страница 12: ...at Address Settings Screen To convert HEX to Decimal code perform the following steps Access the Calculator feature in Microsoft Windows by opening the Start menu Next select Programs then Accessories...

Страница 13: ...HIM to sequentially display two HART variables in five second increments Directly below the Toggle checkbox are two list boxes to select the variables that you would like to be displayed Notice that...

Страница 14: ...ware error or failure has occurred in the connected HART device ConfigurationChanged Bit6 Relay trips whenever it detects that the connected HART device has had its configuration changed Cold Start Bi...

Страница 15: ...s information returned by certain HART instruments This provides flexibility to the requirement of alarming on additional status infor mation Choosing this feature you are given the ability to specify...

Страница 16: ...et the Source as SV Set the Input Range to 0 and 400 F and the Output Range to 4mA to 20mA Click Quick Set to download the new configuration file to the HIM OutputCurrentBox The Output Current Box on...

Страница 17: ...il the analog output matches the minimum point 4mA for a 4 20mA output when you click the Fix Output at Low Point button After the low point is trimmed press the Fix Output at High Point button Read t...

Страница 18: ...tion CustomCurve The middle section of the screen displays the custom curve table After enabling custom curve mode and setting the variable to be monitored continue by selecting the number of points f...

Страница 19: ...er to measure the level of a tank in either centimeters inches or PSI Since the tank is only 300 centimeters 10 feet high the full range of the primary variable PV output from the DP transmitter is 0...

Страница 20: ...r highly skilled staff of trained technicians and engineers pride themselves on their ability to provide timely accurate and practical answers to your process instrumentation questions Factory phone n...

Страница 21: ...a transmission It should be set to match the baud rate of the attached controller The interface supports the following baud rates 300 600 1200 2400 4800 9600 and 19200 Parity The HART monitor supports...

Страница 22: ...RIP 2 TRIP 1 COM DEG C 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC DC GND 24Vdc Power Source DCC R must be 250 ohms and 1100 ohms R HART Field Instrument Temperatur...

Страница 23: ...currentx 100mA HIM Status Information Bit 0 hardware failure Bit 1 EEPROM fail Bit 2 EEPROM configuration checksum error Bit 3 EEPROM calibration checksum error Bit 4 EEPROM blank Bit 5 Out of range...

Страница 24: ...m 2 HART Primary variable float format HART Secondary variable float format HART Third variable float format Hart Fourth variable float format Scaled Primary variable float format Scaled Secondary var...

Страница 25: ...Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 MSB device status LSB device error code Bit Position Description HART device no comms HART device malfunction HW fail EEPROM fail EEPROM checksum error...

Страница 26: ...ance Director Moore Industries Europe General Mgr June 20 2003 Manufacturer sName MooreIndustries International Inc Manufacturer sAddress 16650SchoenbornStreet NorthHills CA91343 6196 USA Declaresthat...

Страница 27: ...OR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT...

Отзывы: