Installation
]
3 Installation
3.1 Notes for installation
ATTENTION!
•
Qualified personnel
Installation must only be carried out by electrical engineering experts
who have been specially instructed in the necessary accident prevention
measures.
•
During installation work
Strictly avoid that ...
− screws, cable rests or foreign bodies drop into the device
− moisture enters into the device
DANGER CAuSED BY HIGH VOLTAGE!
•
Danger to life!
− Never wire or disconnect electrical connections while they are live.
Isolate the device from the mains supply (230/400/460/480 V AC) before
working on it. Even 30 minutes after switching off the mains supply
dangerously high voltages of ≥ 50 V may still be present (capacitor charge).
Work on the device must only be carried out, after the DC link voltage has
dropped below a residual voltage of 50 V (on Size 1-Size 4 to be measured
on terminals X12/L- and L+ or on Size 5 to Size 6A on terminals X12/ZK-
and X12/ZK+, on Size/ on terminals X11/ZK- and X11/ZK+).
− Dangerous voltage may be applied to the device, even if the device does
not emit any visual or audible signals/indications (e.g. with mains voltage
applied to terminal X11) and missing control supply (+24 V on X9/X10 or
X44)!
The following general guidelines apply for the installation of single-axis servo drives:
•
Compliance with the EMC product standard
Commissioning (i.e. starting intended operation) is only permitted when strictly
complying with EMC product standard EN 61800/-3:2004. The installer/operator
of a machine and/or equipment must provide evidence of the compliance with the
protection targets stipulated in the EMC-standard.
•
Cable type
− use only shielded mains, motor and signal lines with double copper braiding that
is overlapping by 60 to 70 %.
− If very large cable cross-sections need to be routed, shielded individual cores
may be used instead of shielded cables.
•
Routing of cable
s
− Route mains, motor and signal cables separated from one another. If possible,
keep a distance of at least 0.2 m, otherwise use separators.
− Always route the motor cable without interruptions and the shortest way out
of the control cabinet. When using a motor contactor or a motor choke, the
respective component should be directly mounted to the servo drive and the
shielding of the motor cable should not be stripped off too soon.
− If possible enter signal lines only from one side into the control cabinet.
− Lines of the same electric circuit must be twisted.
− Avoid unnecessary cable lengths and loops.
•
Grounding
Grounding measures of relevance for the servo drive are described in section 3.5
"Connection PE conductor" on page 24.
• Shielding measures
Do not strip the cable shields too early and attach them amply to both the
component and the PE bar (main ground) of the mounting plate.
•
External components
− Place larger consumers near the supply.
− Contactors, relays, solenoid valves (switched inductivities) must be wired with
fuses. The wiring must be directly connected to the respective coil.
− Any switched inductance should be at least 0.2 m away from the process
controlled assemblies.
Additional information can be found in the corresponding connection description.
If you require further detailed information on installation you should consult the Moog
Helpline (see page 54).
!