15
Installation
XG0225 - 170223
This section applies to installations where the shortest possible vent
run is through the wall. Refer to Appendix A - Power Vent locations,
to ensure the planned Power vent location is acceptable. Refer to the
table below for vent run requirements. Please note, images are shown
without screens for clarity purposes. However, your fireplace should
not be operated without proper installation of screens.
Figure 6.d
Straight Horizontal, Top or Rear Vent, Wall mounted power vent.
Figure 6.f
Multi-Elbow, Top or Rear Vent, Wall mounted power vent.
Figure 6.g
Multi-Elbow with downward vent run, Top or Rear Vent, Wall mounted power vent.
Figure 6.e
PVHIN58-300 Power Vent
PVHIN58-300
Min. 7 feet of pipe between fireplace
and power vent
D**
D**
Section 3-3: Installing a Wall Mounted Vent System
Vent Configuration
Refer to
Figure
Maximum
Vent Run
(Horizontal
+ Vertical)
Maximum
Elbows†
Straight Horizontal Top
or Rear Vent
Figure 6.d
100 Feet
Six 90° or
equivalent
†
Multi-Elbow Top or
Rear Vent
Figure 6.f
Multi-Elbow with 6'
downward vent run
Top or Rear Vent
Figure 6.g
70 Feet**
† One 90° elbow is equal to two 45° elbows.
** For every additional 1 foot downward vent run subtract 10 feet from
the maximum vent run.
Min. 7 feet of pipe between
fireplace and power vent
(6' max)
(6' max)