Page 4
XG0752 - 160902
LDVPV58 Linear Power Vent
2’-0 ”
MIN
Vertical Installed
Linear Power Vent
Horizontal Run Flex Pipe
Vertical
Flex Pipe
90deg
Elbow
90deg
Elbow
90deg
Elbow
Termination
Important:
Maximum Vent Run not to exceed
Seventy feet (70’-0”) feet
.
Installation
Example A.
Vertical Mounting with horizontal Vent Run
Figure 3a.
Vertical Mounting for the Linear Power Venter
Figure 3b.
Horizontal Vent for the Linear Power Venter
Linear Power Vent - Vertical Vent
Multi-elbow installations are possible up to a maximum one-hundred
thirty feet (100'-0"), with three (3) 90° elbows. Minimum vent run from
Fireplace to Power Vent must be two feet, (2'-0"). Maximum allowable
vent run must be reduced by Ten feet (10'-0") for every 90° elbow added.
Figure's 5a and 5b.
12'' Offset box
(SNK58-12)
PT04-PV
PT04-PV
PT04-PV
PVTK1SS
PVTK1SS
PT04-PV
12'' Offset box
(SNK58-12)
Example B.
Horizontal Mounting with horizontal Vent Run
Linear Power Vent - Horizontal / Downward Vent
Multi-elbow installations are possible up to a maximum seventy feet
(70'-0"), with three (3) 90° elbows. Minimum vent run from Fireplace to
Power Vent must be two feet, (2'-0"). Maximum allowable vent run must
be reduced by Ten feet (10'-0") for every 90° elbow added. Deduct ten
feet (10'-0") of vent length for every one foot (1'-0") of vent run traveling
in a downward direction.
Figure 4a
. Horizontal Linear Power Vent with Horizontal Vent Run
Figure 5a.
Vertical Vent for the Linear Power Venter
Example A.
Vertical Mounting with Vertical Vent Run
2’-0 ”
MIN
Vertical Installed
Linear Power Vent
Vertical
Flex Pipe
90deg
Elbow
90deg
Elbow
90deg
Elbow
90deg
Elbow
Termination
Important:
Maximum Vent Run not to exceed
Seventy (70’-0”) feet.
2’-0 ”
MIN
Example B.
Vertical Mounting with Vertical Vent Run
Figure 5b.
Vertical Linear Power Vent with Vertical Vent Run
Vertical Installed
Linear Power Vent
Vertical
Flex Pipe
90deg
Elbow
90deg
Elbow
90deg
Elbow
90deg
Elbow
Important:
Maximum Vent Run not to exceed
Seventy (70’-0”) feet.
Termination
2’-0 ”
MIN
Horizontal Installed
Linear Power Vent
Horizontal Run Flex Pipe
Vertical
Flex Pipe
90deg
Elbow
90deg
Elbow
90deg
Elbow
Termination
Important:
Maximum Vent Run not to exceed
Seventy feet (70’-0”) feet.
Available
Option
Horizontal Installed
Linear Power Vent
Horizontal Run Flex Pipe
Vertical
Flex Pipe
90deg
Elbow
90deg
Elbow
Termination
Important:
Maximum Vent Run not to exceed
Seventy feet (70’-0”) feet.
6’-0 ”