Page 8
H52-DF Gas Fireplace
Part No. XG0650
Installation
WARNING
:
All venting material must be sealed with high heat silicone sealant
RV230. All venting material to be Montigo flex pipe, with as few
joints as possible. All joints use MVA vent splice, sealed thoroughly
with silicone.
WARNING
:
Montigo will not be held responsible for any water damage that
may occur from not installing the equipment as specified by
this document.
Linear Power Vent - Horizontal Vent
Multi-elbow installations are possible up to a maximum Seventy feet
(70'-0"), with three (3) 90° elbows. Minimum vent run from Fireplace
to Power Vent must be two feet, (2'-0"). Maximum allowable vent run
must be reduced by Ten feet (10'-0") for every 90° elbow added. With
a snorkel Termination, reduce the total vent run by an additional twenty
feet (20'-0"). Figure's 6a and 6b.
Example A.
Vertical Mounting with horizontal Vent Run
Figure 6a.
Vertical Mounting for the Linear Power Venter
Figure 6b.
Horizontal Vent for the Linear Power Venter
Example B.
Horizontal Mounting with horizontal Vent Run
Linear Power Vent - Horizontal / Downward Vent
Multi-elbow installations are possible up to a maximum seventy feet
(70'-0"), with three (3) 90° elbows. Minimum vent run from Fireplace to
Power Vent must be two feet, (2'-0"). Maximum allowable vent run must
be reduced by Ten feet (10'-0") for every 90° elbow added. Deduct ten
feet (10'-0") of vent length for every one foot (1'-0") of vent run traveling
in a downward direction.
Figure 7a
. HorizontaI Linear Power Vent with Horizontal Vent Run
Linear Power Vent - Vertical Vent
Multi-elbow installations are possible up to a maximum seventy feet
(70'-0"), with three (3) 90° elbows. Minimum vent run from Fireplace to
Power Vent must be two feet, (2'-0"). Maximum allowable vent run must
be reduced by Ten feet (10'-0") for every 90° elbow added. Figure's 8a
and 8b.
Figure 8a.
Vertical Vent for the Linear Power Venter
Example A.
Vertical Mounting with Vertical Vent Run
2’-0”
MIN
Vertical Installed
Linear Power Vent
Horizontal Run Flex Pipe
Vertical
Flex Pipe
90deg
Elbow
90deg
Elbow
90deg
Elbow
Termination
Snorkel
Termination
Important:
Maximum Vent Run not to exceed
Seventy feet (70’-0”) feet
.
LDVPV58
LDVPV58
Horizonta
l
Insta
ll
e
d
Linear Power Vent
Horizontal Run Flex Pipe
Vertical
Flex Pipe
90deg
Elbow
90deg
Elbow
90deg
Elbow
Termination
Snorkel
Termination
Important:
Maximum Vent Run not to exceed
Seventy feet (70’-0”) feet
.
Available
Option
Horizontal Installed
Linear Power Vent
Horizontal Run Flex Pipe
Vertical
Flex Pipe
90deg
Elbow
90deg
Elbow
Termination
Important:
Maximum Vent Run not to exceed
Eighty feet (80’-0”) feet.
6’-0”
LDVPV58
2’-0 ”
MIN
Vertical Installed
Linear Power Vent
Vertical
Flex Pipe
90deg
Elbow
90deg
Elbow
90deg
Elbow
90deg
Elbow
Termination
Important:
Maximum Vent Run not to exceed
Seventy (70’-0”) feet
.
2’-0 ”
MIN
LDVPV58