Page 11
H52-DF Gas Fireplace
Part No. XG0650
Installation
Finishing Around the Fireplace
Combustible mantels and mouldings may be safely installed over the
top and on the front of the fireplace provided that they do not project
beyond shaded area shown in
Figure 13
. Side wall clearances are 3".
Combustible surrounds may be installed with 3" clearance to the side
of the fireplace as shown in
Figure 14
.
Figure 13.
Combustible mantles and facings.
Fireplace Facing
When selecting the finish material for your fireplace, it is important to
remember the following:
If the surround of the fireplace is to be painted to match the room decor,
heat-resistant paint must be provided . Also, decorative facing must not
extend past the fireplace opening at all, because it will interfere with the
access to retainers for removal of glass door and access to the lower
compartment.
Mantels & Surrounds
NOTE:
National Canadian Gas Association mantel test requirements
are for fire hazard prevention to combustible materials.
New technology, to meet consumer and government demands for the
wise use of energy, has prompted us to manufacture many models of
fireplaces which are hot, fuel and energy efficient.
Please be aware; temperatures over the mantel will rise above normal
room temperature and walls above fireplace may be hot to touch.
Warning:
When covering the upper metal portion of the fireplace, up to 6" (
as
shown, Fig.13 & Fig.14
, with a non-combustible material Please Note: The
decorative facing materials may be subject to temperatures in excess of
250° F. This should be considered when selecting facing materials.
We recommend careful consideration be given to the effects of elevated
mantel temperatures which may be in excess of product design, for
example: candles, plastic or pictures. This can cause melting, deformation,
discoloration or premature failure of T.V. and radio components.
Horizontal Run (in)
Figure 12.
Wiring schematic for the Post Purge Control Module ECB006.
Strain Relief
Wall Switch
Air Proving
Switch
Fuse
G
L2
L1
Bk
Bl
Bl
Bk
Bk
Bk
Bk
TDR
TDR Coil
R
R
R
W
W
W
W
W
Transformer
Strain Relief
115V
24V
Gas Control Connector
M1
BX Conduit
Main Junction Box
Receptical
To 115V AC Supply
Legend
Denotes Line Voltage
Denotes Low Voltage
Denotes Wire Connector
Air Switch
M2
F
F
W
Bk
Power Vent
Fireplace
Steel Stud construction
allowable within this area
Non-Combustible
Facing Material