Page 6
H52-DF Gas Fireplace
Part No. XG0650
Installation
PTKOG
(5"/8")
1. Ensure that the two
long
mounting brackets are facing the bottom
of the termination. (See inset). This will provide more heat protection
at the top of the termination, where temperatures are highest.
2. Attach to the faceplate of the termination using four sheet metal
screws.
Installing Heat Guards over Terminations
Installing The Power Vent
The LDVPV58 Linear Power Vent System must ONLY be used with
a Montigo H52-DFN Direct Vent Fireplace. When selecting Venting
components for use with this Linear Power Vent System, take into con
-
sideration the various requirements and limitations in the vent installation
section of the Model's manual:
Models Must Be Equipped with Electronic Ignition
(HSI/AF)
Only models equipped with an electronic ignition system may be installed
with the LDVPV58 Linear Power Vent System. The absence of a pilot in
this system, allows for greater flexibility on venting requirements.
General Information
This installation section covers installation of the LDVPV58
Linear Power
Vent System ONLY. This system is designed to allow the installation of the
H52-DFN gas fireplace to function with many years of reliable service.
Specifications and instructions pertaining SPECIFICALY to the H52-DFN
fireplace must be followed. Please read these Installation Operation
and Maintenance Instructions thouroughly and carefully before operat
-
ing this equipment.
Standard Series (5"/8" dia.) Termination System:
LDVPV58 - Linear Power Vent System
Pre/Post Purge Control Box
RHSIT05 -Control module, provides pre/post purge.
Power Cord Harnesses:
LPVH10 -10 foot power cord and harness
LPVH20 -20 foot power cord and harness
LPVH30 -30 foot power cord and harness
LPVH40 -40 foot power cord and harness
LPVH50 -50 foot power cord and harness
LPVH60 -60 foot power cord and harness
LPVH70 -70 foot power cord and harness
LPVH80 -80 foot power cord and harness
Before You Begin
Minimum clearances of 1" from vent to all combustible materials
must be maintained.
The LDVPV58 must only be installed with Montigo venting
components as specified in these instructions.
In order to maintain the power vent system integrity all 5" and 8"
venting connections must also be sealed with high temperature
silicone.
Installation of the LDVPV58 must comply with this manual, and
be completed by a qualified professional.
The MAXIMUM total allowable length; Refer to Linear Power
Vent Installation Section, 3-4.
Minimum length of straight pipe between the Fireplace and the
Power Vent is: 2 feet
Access / Service Panel, must maintain 2" clearance. If 2" clearance
is not possible Minimum 30% free air must be supplied.
Disconnect the power supply when installing and/or servicing
the fireplace or the power vent system.
The DVPV58 termination is designed
to be Installed flush with the exterior of
the building. This recessed design uses
5"/8" vent and allows the installation to
be clean and flush so it does not interfere
or have an impact with your architectural
design.
Note: The Louvred grille is not supplied by
Montigo and must be sized accordingly.
We require a MIN 80in/sq free air
movement to adequately allow air to
enter, and exhaust the fireplace. Also note
the material of the louvre must be able to
withstand high operating temperatures.
IMPORTANT
The H52-DFN requires a specific volume of atmospheric
interchange to operate properly and efficiently.
The fireplace requires a MIN 80in/sq. air movement
■
to function.
Due to high operating temperatures the louvered
■
grill must be manufactured from a material that will
be capable of withstanding high temperatures.
The grille must also be able to shed water, not
■
allowing any moisture to enter the unit.
Recessed Termination Installation
(DVPV58)
Figure 5
. Linear Power Vent recessed Termination.