   HORIZONTAL VENTING

**NOTE:

All dimension lengths for vertical or horizontal
runs are measured from center of the 7" elbow.

All vent pipes must maintain a minimum of 1" clearance to
combustible materials.

Horizontal length (see venting graph)

C

F

Vertical length (see venting graph)

A

B

10"

4"

E

D

B

A

43"

10 Ft Section
   MIHR-10

  12 1/2 Ft.
  07 1/2 Ft.

6 Ft Section
   MIHR-6

  8 1/2 Ft.
  3 1/2 Ft.

Center of 7" elbow
to outside wall

Maximum extended length
Maximum retracted length

FIGURE 5.    TYPICAL INSTALLATIONS.

Header

10 ft. from center of elbow

12 1/2 ft. from center of fireplace

Stucco Can
Vent Termination

3 ft. flex section

B

Solid section includes

90 degree elbow

Hearth

Wall Thickness

(4" - 12")

A

FIGURE 6.  EXTENDED 10' SECTION

7 1/2 ft. from

center of fireplace

3 ft. flex

 section

10 ft. from center of elbow

A

B

Stucco Can
Vent Termination

Solid section includes

90 degree elbow

Hearth

FIGURE 7.  RETRACTED 10' SECTION

10' Max

FIGURE 8.TYPICAL VENT TERMINATIONS

AND FIREPLACE LOCATIONS

Stucco Can
Vent Termination

3 ft. Max

3, or 4 ft. flex section
turned 90 degrees.

FIGURE 7.1  HORIZONTAL FLEX

     INSTALLATION

Содержание ECONO-PLUS 36DV-TV

Страница 1: ...R YOUR SAFETY IF YOU SMELL GAS 1 OPENWINDOWS DONOTSTOREORUSEANYFLAMMABLE 2 DON TTOUCHELECTRICALSWITCHES VAPOURSORLIQUIDSNEARTHISORANY 3 EXTINGUISHANYOPENFLAME OTHERGAS BURNINGAPPLIANCE 4 IMMEDIATELYCALLYOURGASSUPPLIER READ INSTRUCTIONS CAREFULLY BEFORE INSTALLING MODEL MONTIGO36DV TV CANADIAN HEATING PRODUCTS INC 12091 88th Avenue Surrey B C Canada Phone 604 597 3115 Fax 604 597 3096 ...

Страница 2: ... SEEFIGURE2FORFRAMINGDIMENSIONS FIGURE 1 FIREPLACE DIMENSIONS CAUTION The gas line must be installed before finishing the Montigo 36DV TV Fireplace Natural Gas requires an inlet pressure of 7 W C a manifold pressure of 3 5 W C Propane Gas requires an inlet pressure of 11 W C a manifold pressure of 10 5 W C It is also required that provisions be made for a 1 8 N P T plugged tapping and be accessabl...

Страница 3: ...mbustible materials Note It is imperative for satisfactory operation of the Montigo 36DV TV fireplace that no venting component be modified in any way All components have been manufactured to eliminate the need for modification when properly selected and installed CAUTIONS AND REQUIREMENTS DIRECT VENT TERMINATION LOCATION This section is used to determine where your direct vent termination will be...

Страница 4: ...ngth Maximum retracted length FIGURE 5 TYPICAL INSTALLATIONS Header 10 ft from center of elbow 12 1 2 ft from center of fireplace Stucco Can Vent Termination 3 ft flex section B Solid section includes 90 degree elbow Hearth Wall Thickness 4 12 A FIGURE 6 EXTENDED 10 SECTION 7 1 2 ft from center of fireplace 3 ft flex section 10 ft from center of elbow A B Stucco Can Vent Termination Solid section ...

Страница 5: ... Plate Ring E 7 Firestop FS 7 7 Firestop F Roof Flashing MRF 16 1 12 to 6 12 pitch MRF 12 6 12 to 12 12 pitch VERTICAL DIRECT VENT TERMINALS Shall not be installed Less than two feet above the highest point where vent passes through the roof Less than six feet from a mechanical air inlet Less than three feet from a parapet wall Offsets A maximum of two offsets with 90 degree bends may be made and ...

Страница 6: ...nlets A B C Horizontal Vertical VENTING GRAPH VENTING GRAPH Venting graph is used for top vent direct vent model only How to use the venting graph 1 Determine the height for the centre of the 7 vent elbow and mark a horizontal line until it intersects with the slanted graph line 2 From the point of this intersection draw a vertical line to the bottom line of the graph 3 Select the indicated dimens...

Страница 7: ...combustion door NOTE National Canadian Gas Association mantel test require ments are for fire hazard prevention to combustible materials New technology to meet consumer and government demands for the wise use of energy has prompted us to manufacture many models of fireplaces which are hot fuel and energy efficient Please be aware temperatures over the mantel will rise above normal room temperature...

Страница 8: ...lar shaped extension into the log rest located on rear wall of the burner assembly Place the slot of log B over the pilot runner bar located on the left hand front side of the burner assembly Next place logs C and D onto mating positions of logs A and B as shown below FAILURETOINSTALLLOGSASINSTRUCTEDMAY RESULTINEXCESSIVESOOTING FIGURE 13 SAFETY LOCK Knotch Door Turn Turn FIGURE 12 INNER GLASS DOOR...

Страница 9: ...ust be cleaned periodically Film can easily be removed by removing inner and outer doors handling carefully and cleaning with normal liquid household products WARNING Do not attempt to clean glass when hot Do not clean glass with abrasive materials as any glass etching may cause premature glass failure Silicone seals on inner door during initial firing will off gas leaving a visual deposit of a wh...

Страница 10: ...se The decorative gas appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the decorative gas appliance will produce excessive temperatures and will result in a fire hazard LIMITATIONS ON LIABILITY It is expressly agreed and understood that Canadian Heating Products Inc s sole obligation and purchaser s exclusi...

Отзывы: