Installation
Installation Of Electrical Supply
The
BF36
Fireplace is supplied with an external electrical Control
Panel pre-wired by the factory. The standard gas control cable is 15
feet between the fireplace and the external panel, additional length
is available upon request. The external panel is 16" x 16" x 6" and
must be located in an accessible location. The C-View requires
120V
electrical supply on a dedicated 15 amp fuse or circuit breaker
to
the Control Panel.
Installations in Canada
must be electrically grounded in accordance
with
CSA C22.1
Canadian Electrical Code Part 1 and/or Local Codes.
Installations in the USA
must be electrically grounded in accordance
with local codes or, in the absence of local codes, with the National
Electrical Code,
ANSI/NFPA 70-1987.
The electrical panel has three connection boxes on the side of the
panel marked: 110 Volt Power Supply, Power Vent Motor, and Gas
Control Wiring.
First Connect the White, Black, and Green (Ground) wire coming
from the power vent motor in the box marked Power Vent Motor. Then
connect the cable from the fireplace. Last connect the power supply
to the box marked 110 Volt Power Supply. See the diagram on
page
7
for the cable installation.
Installing The Remote Switch
The
BF36'
s two gas valves, located inside the unit and underneath
the burner, may be connected to a wall switch or a hand-held remote.
The valve operates on
a
24V circuit. DO NOT
connect the gas valve
to an external circuit. The external electrical panel supplied with the
fireplace is equipped with a 20 foot low voltage wire, for connecting to
a wall switch of your choice, longer lengths are an option.
Figure 7.
Electrical Supply
110V Power Supply
Power Vent Motor
Gas Control Wiring
Wall Switch
Air Proving Switch
Fuse
Fan Speed
Control
Post Purge
Control
Vent Terminations
Selecting A Termination Location
Before installing the termination or venting, check to ensure the
planned termination location is acceptable. See
figure 10 & 10a
below.
Vent Installation
General Installation Requirements
The
BF36
fireplace is certified for use with any approved 12" B-
Vent venting components. (Use information below for 'With door'
application)
1" clearance to combustibles
for vent pipes on all vent runs, or
use the clearances specified by the B-Vent manufacturer, which-
ever is greater.
This Power Vent system will depressurize the building at 1800
CFM, and a sufficient air intake system must be installed to avoid
any malfuntion of other appliances that rely on room air.
This fireplace is a sealed unit and will not effect or alter the build-
ing air system. However due to the large amount of air that moves
through the fireplace the net gain will be very small.
Installation Requirements
(With & Without door)
Use only
certified B-Vent vent components.
(Use of other parts
will void the Montigo warranty, and may impede the operation of
the fireplace).
All joints must be secured as per the instructions provided by the
B-Vent manufacturer.
The exhaust portion of a vent termination must not be recessed in
walls or siding.
Horizontal runs must be supported by a minimum of three sup-
ports per 10 feet of venting.
Each Vertical Venting installation may have up to four 90° elbows.
Each Horizontal Venting installation may have up to three 90°
elbows.
Two 45° elbows consist of one 90° elbow.