BF36 SS and ST Gas Fireplace
Part No. XG0712 - 031811
f i r e f e a t u r e
Installation
Figure 7
.
Typical B-vent configurations.
Combustion Air Supply System
Installation Requirements
An intake grill will have to be installed with the same size of the total opening
as the combined air supply ducts on the unit. Make sure you have calculated
the restriction and selected the proper grill size.
The
BF-SS
fireplace is supplied with two or more combustion air duct
connection points. Do not reduce the size of the air supply system, or
restrict the air supply in any way. On any combustion air supply run longer
than 10 feet the duct should be increased in size to prevent a restriction.
A vacuum safety switch, located under the burners, will monitor the combustion
air supply pressure and will prevent the burner from igniting, or continuing
to burn if the pressure is negative, past 0.08WC.
For extremely long air supply runs the combustion air supply will have to
be power assisted.
Figure 7b.
BF-SS
Standard Control Box
Power Vent Control Box
Wiring requirements for Power Vent Installation
Power Vent
Termination
Power Vent
Termination
16”x 16”x 4”
Deep Elect.
Control Box
One Control Cable Installation
required for either Horizontal
or Vertical Termination.
From Control Box
20’ Foot, 10-Conductor
Cable to Fireplace,
(Standard)
110 VAC 15A
Supply Current
From Dist. Panel
To
Control Box
Exterior Power Vent / Wire
Routing Installation Diagram
Figure 7a.
BF-SS
Control Box / Power Vent Wire Routing Diagram)
12”
Power Vent
Termination
Power Vent
Termination
12” B-Vent Duct, One run
for Horizontal or Vertica
l
Installation Required
.