7.4.
Monodraught COOL-PHASE Service Points:
Run test program and review all functions.
The elliptical fan will be checked for correct operation.
Thermal Battery performance verification.
Firmware updated to latest revision.
Check all sensors operating within parameters, and re-calibrate if necessary.
COOL-PHASE System, Thermal Batteries and ductwork checked for cleanliness.
Filter change.
Data logs downloaded for optional performance case study.
Correct operation of actuators within the recirculation module.
Correct operation of Rotational Air Drum.
The COOL-PHASE system is considered a fixed piece of equipment and is therefore not subject to
PAT testing.