Summary Table:
9.
Decommissioning / Dismantling Requirements:
9.1. PCM Modules and Air Handling Unit
The COOL-PHASE system can be dismantled with relative ease separating the various materials. The
expanded polypropylene (EPP), aluminium and steel used within the system are all suitable for
recycling. The insulated duct work is safe to be disposed of in general waste.
9.2. Electronics and Electrical Components
The electronic components used to control the COOL-PHASE system under the WEEE/EA0749YY
directive can be sent back to Monodraught for disposal and recycling
.
Season
Spring
Summer
Autumn
Winter
Start Date
01-March
1-June
1-Sept
01-Dec
Finish Date
31- May
30 - August
30-Nov
Last day of Feb
Occupied
hours (Day
time)
Cooling provided
when room
temperature
reaches > 23°
Ventilation
provided when
internal CO2
levels reaches >
900 ppm
Cooling provided
when room
temperature
reaches > 22°
Ventilation
provided when
internal CO2
levels reaches >
800 ppm
Cooling provided
when room
temperature
reaches > 23°
Ventilation
provided when
internal CO2
levels reaches >
900 ppm
Cooling provided
when room
temperature
reaches > 24°
Ventilation
provided when
internal CO2
levels reaches >
1000 ppm
Un-occupied
hours
(Night Time)
PCM recharge
mode
Summer recharge
mode and pre-
cooling of the
space.
PCM recharge
mode
Heat recovery
mode, or winter
recharge mode.