FG073
– DELTA CONT. RevA17 10-4-17
49
Check the 3
status LED’s:
RED
OFF
YELLOW
ON
GREEN
ON
Still with zero speed command signal, adjust the offset pot until the MC
(machine command signal) and the ENC (encoder counts) for the axis concerned
are stable and at or near 0000 readout. These are displayed at the bottom of the
screen. Periodically re-check this setting throughout the following procedure.
Connect digital storage oscilloscope to the test points command and OV on the
amplifier unit and select a suitable voltage scale to measure the command signal
from the controller to the amplifier. Obtain password protected
`max speed Set up’
menu (see fig. 1a and 1b) to enable a maximum speed signal to all 4 motors at
once.
Once again it is imperative that the `head raise / lower’ motor is
decoupled
- see CAUTION.
Addressing each motor in turn adjust the Command and/or Tacho Gain pots to
give a command signal value from the controller to the amplifier of 9.5V.
Press stop
to cease command.
Again with the
`max speed signal’
menu driving all four motors at full speed,
adjust the Stability potentiometer to give as smooth a command signal from the
controller as possible. Press stop to cease command.
Adjust Peak Current pot accordingly.
Axis 0 (Deposit Pump)
fully clockwise
Axis 1 (Tray Conveyor) - ½ way clockwise
Axis 2 (Head raise/lower) - fully clockwise
Axis 3 (Rotary nozzle) - ½ way clockwise
All values once set should not need readjustment.
FIELD SET UP (Amplifier replacement) CAUTION
Extreme care must be exercised when applying these procedures to machine mounted
motors to avoid incurring damage to the machine, drive and/or motor. If at all possible
the initial set-up should be performed with the motor decoupled from the machine
and/or drive components.
To minimise the amount of setting-up required during commissioning or when replacing a
drive on site the majority of the adjustments have been incorporated on a removable
personality module. This means that when a drive is replaced on site it is simply necessary
to take the personality module from the old drive and fit it on to the new drive. The only
adjustments that remain to be done are Offset and Gain. These are altered by means of two
pots, the Offset pot being on the main pcb and the Gain pot being on the personality
module.