Monessen  • Glow Getter Owner’s /Installation Manual  •  4606-900  Rev. A  •  8/17

NOTE REGARDING VENTED PRODUCTS

This product must be installed by a licensed plumber or 

gas fitter when installed within the Commonwealth of 

Massachusetts.

Any residence with a direct vent product must have a carbon 

monoxide (CO) detector installed in the residence.
Installation of the fireplace or vented gas log in the State 

of Massachusetts requires the damper to be permanently 

removed or welded in the fully open position.

In addition, a naturally vented gas log may not be installed in a 

bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve. 

NOTE REGARDING VENT FREE PRODUCTS

This product must be installed by a licensed plumber or 

gas fitter when installed within the Commonwealth of 

Massachusetts.

In addition, vent free products may not be installed in a 

bedroom or bathroom regardless of size or type in the State of 

Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve.

CARBON MONOXIDE DETECTOR REQUIREMENTS

(2) Revise 10.8.3 by adding the following additional 

requirements:
(a)  For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in whole 

or in part for residential purposes, including those owned 

or operated by the Commonwealth and where the side wall 

exhaust vent termination is less than seven (7) feet above 

finished grade in the area of the venting, including but not 

limited to decks and porches, the following requirements shall 

be satisfied:

1. 

Installation of carbon monoxide detectors. 

At the time 

of installation of the side wall horizontal vented gas fueled 

equipment, the installing plumber or gas fitter shall observe 

that a hard wired carbon monoxide detector with an alarm and 

battery back-up is installed on the floor level where the gas 

equipment is to be installed. In addition, the installing plumber 

or gas fitter shall observe that a battery operated or hard wired 

carbon monoxide detector with an alarm is installed on each 

additional level of the dwelling, building or structure served 

by the side wall horizontal vented gas fueled equipment. It 

shall be the responsibility of the property owner to secure the 

services of qualified licensed professionals for the installation 

of hard wired carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 

hard wired carbon monoxide detector with alarm and battery 

back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can not be met at the time of completion of installation, the 

owner shall have a period of thirty (30) days to comply with the 

above requirements; provided, however, that during said thirty 

(30) day period, a battery operated carbon monoxide detector 

with an alarm shall be installed.

MASSACHUSETTS RESIDENTS ONLY

2. 

Approved Carbon Monoxide Detectors.

 

Each carbon 

monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.

3. 

Signage.

 A metal or plastic identification plate shall 

be permanently mounted to the exterior of the building at a 

minimum height of eight (8) feet above grade directly in line 

with the exhaust vent terminal for the horizontally vented gas 

fueled heating appliance or equipment. The sign shall read, in 

print size no less than one-half (1/2) inch in size, “GAS VENT 

DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

4. 

Inspection.

 The state or local gas inspector of the 

side wall horizontally vented gas fueled equipment shall not 

approve the installation unless, upon inspection, the inspector 

observes carbon monoxide detectors and signage installed 

in accordance with the provisions of 248 CMR 5.08(2)(a)1 

through 4.
(b) 

Exemptions:

 The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled "Equipment 

Not Required To Be Vented" in the most current edition of 

NFPA 54 as adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled 

equipment installed in a room or structure separate from the 

dwelling, building or structure used in whole or in part for 

residential purposes.
(c)  

Manufacturer requirements — Gas Equipment Venting 

System Provided.

 

When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides 

a venting system design or venting system components with 

the equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system shall 

include:

1. Detailed instructions for the installation of the venting 

system design or the venting system components; and

2. A complete parts list for the venting system design or 

venting system.
(d) 

Manufacturer requirements — Gas Equipment Venting 

System Not Provided. 

When the manufacturer of a Product 

Approved side wall horizontally vented gas fueled equipment 

does not provide the parts for venting the flue gases, but 

identifies “special venting systems,” the following requirements 

shall be satisfied by the manufacturer:

1. The referenced "special venting system" instructions 

shall be included with the appliance or equipment installation 

instructions; and

2. The “special venting systems” shall be Product Approved 

by the Board, and the instructions for that system shall include 

a parts list and detailed installation instructions.
(e)  A copy of all installation instructions for all Product 

Approved side wall horizontally vented gas fueled equipment, 

all venting instructions, all parts lists for venting instructions, 

and/or all venting design

Please read and follow these special requirements

Содержание GG18NV

Страница 1: ...e DO NOT store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance What to do if you smell gas DO NOT try to light any appliance DO NOT touch any elec...

Страница 2: ...Millivolt Ignition Controls 7 G Pilot ODS 7 H Adequate Combustion Ventilation Air 8 3 Clearances Height Requirements A 9 4 Gas Information A Gas Line Connection 15 B Millivolt Valve Controls 15 C Fue...

Страница 3: ...____________________ ___________________________ ___________________________ Finishing Section 3 Pg 9 Verified all clearances meet installation manual requirements Mantels and wall projections comply...

Страница 4: ...PV LABORATORY CSA TYPE Unvented Room Heater STANDARD ANSI Z21 11 2 2016 Unvented Application ANSI Z21 60 2012 CSA2 26 2012 Vented Application Models Maximum Input BTU h Minimum Input BTU h Front Orif...

Страница 5: ...be sure that the following tools and building supplies are available Tape measure Gloves Voltmeter Manometer Phillips screwdriver Safety glasses Flat blade screwdriver Soapy water solution for gas le...

Страница 6: ...install this appliance in a factory built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs WARNING Model A B C D GG18 with LOGS 27 14 2...

Страница 7: ...in front of a gas log set can change the air flow characteristics of the fireplace which in turn can cause the unit to overheat and malfunction when installed as a vented log set WARNING Glass door fr...

Страница 8: ...ous water vapor retarder with a rating of 1 perm 6 x 1011 kg per pa sec m2 or less with openings gasketed or sealed and b Weather stripping has been added to windows and doors and c Caulking or sealan...

Страница 9: ...resistant Material Measure This Distance Heater in Fireplace Firebox Figure 3 2 Measure Heat Resistant Material Table A Heat Resistant Material Requirements with No Mantel or Combustible Projection H...

Страница 10: ...r Combustible Projection GG18 GG24 12 or more Hood not required Observe profiles side elevations shown in Figure 3 4 Hood not required Observe profile side elevations shown in Figure 3 6 8 or less tha...

Страница 11: ...f 21 2 at a minimum of 14 above the opening and a maximum of 6 at a minimum of 201 2 above the opening Figure 3 4 Minimum Mantel Clearance with No Hood GG18 Heat Resistant Material Heater in Fireplace...

Страница 12: ...arer to the floor if a minimum of 14 of noncombustible material such as slate or marble is installed between the base of the fireplace and the combustible flooring Figure 3 8 Figure 3 7 Minimum Cleara...

Страница 13: ...a heat resistant sealant Install and operate the appliance as directed in this manual Damper stop installation Adamper stop must be provided with the unit Contact your dealer to obtain one The damper...

Страница 14: ...n the fireplace or firebox floor Drill two 2 5 32 diameter holes approximately 1 deep Anchor the two anchoring screws shipped with the unit using hex head chuck and secure the burner assembly to the f...

Страница 15: ...ontrol set to HIGH B Millivolt Valve Control The valve regulator controls the burner pressure which should be checked at the pressure test point Turn captured screw counter clockwise two or three turn...

Страница 16: ...sure will damage valve Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1 2 psig Close the manual shutoff valve BEFORE pressure testing gas line at test pressures...

Страница 17: ...ne wire to TH using fork terminal or connect the wall switch thermostat to the two male 0 25 terminals on the left side of the unit The color of the wires does not matter Figure 4 3 Wiring Diagram NOT...

Страница 18: ...to terminals as indicated 1 Complete Millivolt System Check A Reading Thermostat contacts CLOSED Control Knob ON Main burner should turn ON a If the reading is more than 175 millivolts and the automa...

Страница 19: ...emove any traces of fibers The positioning of the logs is critical to the safe and clean operation of this heater Sooting and other problems may result if the logs are not properly and firmly position...

Страница 20: ...le on the bottom of the log over the pin on the left hand side and push back against the rear bend on the sheet metal of the burner assembly See Figure 5 3 4 Hold log 3 with your left hand with the fa...

Страница 21: ...of log 4 See Figure 5 7 6 Figure 5 7 Log 6 Placement 8 Hold log 7 with the pointed end to the left and the flat end toward the bottom Place log 7 by positioning the two pin locator holes on the botto...

Страница 22: ...g 1 and by sliding the wide end toward the back When in place the left rear of log 5 should come in contact with log 4 and the left side of the slot on log 1 It should match with log 4 See Figure 5 15...

Страница 23: ...d last four hours with the burner at the highest setting Provide maximum ventilation by opening windows or doors to allow odors to dissipate Any odors remaining after this initial break in will be sli...

Страница 24: ...ice DO NOT store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance What to do if you smell gas DO NOT try to light any appliance DO NOT touch any el...

Страница 25: ...to provide the utmost in safety efficiency and style As the owner of a new vent free log set you ll want to read and carefully follow all of the instructions contained in this owner s manual Pay spec...

Страница 26: ...on the date of original purchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an indepen...

Страница 27: ...RANTY EXCLUSIONS This warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes...

Страница 28: ...re are at risk individuals in the house To restrict access to a fireplace install an adjustable safety gate to keep toddlers young children pets and other at risk individuals out of the room and away...

Страница 29: ...cal codes with the National Fuel Gas Code ANSI Z223 l NFPA54 11 This unit complies with ANSI Z21 11 2 Unvented Heaters latest edition and ANSI Z21 60 2012 CSA2 26 2012 12 Do not install the heaters in...

Страница 30: ...0 Input ratings are shown in BTU per hour and are for elevations up to 4 500 feet For elevations above 4 500 each 1 000 feet above sea level Refer to the National Fuel Gas Code 21 The appliance and it...

Страница 31: ...o ANSI standards for Unvented Room Heaters and applicable sections of Gas Burning Heating Appliances for Manufactured Homes and Recre ational Vehicles and Gas Fired Appliances for Use at High Altitude...

Страница 32: ...ach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it Call a q...

Страница 33: ...to allow air to bleed out of the gas piping 7 With the control knob pushed in push in and release the piezo ignitor button to light the pilot 8 Continue pushing the control knob in for a further 60 se...

Страница 34: ...priate lighting instructions found previously Instead of pushing and releasing the piezo button light a match and hold the flame to the end of the pilot and ignite the pilot 3 After control knob has b...

Страница 35: ...of trouble free service Contact your dealer to answer questions regarding proper operation trouble shooting and service for your appliance Visit www mon essenhearth com to locate a dealer We recommen...

Страница 36: ...g carefully by holding gently at each end Gloves are recommended to prevent skin irritation from logs If skin becomes irritated wash gently with soap and water Refer to manual for correct log placemen...

Страница 37: ...e Appliance shuts off during use Not enough fresh air is available for ODS pilot to operate Open window and or door for ventilation Low line pressure Contact local gas company ODS pilot is partially c...

Страница 38: ...8 17 38 12 Service Parts A Service Parts Service Parts GG18NV Beginning Manufacturing Date Sept 2017 Ending Manufacturing Date Active Part number list on following page 09 17 Glo Getter 18 Hearth Kit...

Страница 39: ...25 4 Piezo 14D0503 Y 5 Assembly Wire 00K0632 Y 6 Burner Pan Assembly NG SRV4606 026 Y 7 Media Retainer SRV4606 105 8 Burner Bracket Side Pin SRV4606 115 9 Tube Burner Assembly SRV4606 025 Y 10 Tube Va...

Страница 40: ...nual 4606 900 Rev A 8 17 40 Service Parts GG18PV Beginning Manufacturing Date Sept 2017 Ending Manufacturing Date Active Part number list on following page 09 17 Glo Getter 18 Hearth Kit 1 2 5 3 4 6 7...

Страница 41: ...dment SRV4606 021 3 Mesh Cover SRV4606 125 4 Piezo 14D0503 Y 5 Assembly Wire 00K0632 Y 6 Burner Pan Assembly LP SRV4606 028 Y 7 Media Retainer SRV4606 105 8 Burner Bracket Side Pin SRV4606 115 9 Tube...

Страница 42: ...ual 4606 900 Rev A 8 17 42 Service Parts GG24NV Beginning Manufacturing Date Sept 2017 Ending Manufacturing Date Active Part number list on following page 09 17 Glo Getter 24 Hearth Kit 1 2 3 4 5 6 7...

Страница 43: ...Cover SRV4606 125 4 Piezo 14D0503 Y 5 Assembly Wire 00K0632 Y 6 Burner Pan Assembly NG SRV4606 003 Y 7 Media Retainer SRV4606 105 8 Burner Bracket Side Pin SRV4606 115 9 Tube Burner Assembly SRV4606...

Страница 44: ...Manual 4606 900 Rev A 8 17 44 Service Parts GG24PV Beginning Manufacturing Date Sept 2017 Ending Manufacturing Date Active Part number list on following page 09 17 Glo Getter 24 Hearth Kit 1 2 3 4 5 6...

Страница 45: ...14D0477 Y 2 Grate Weldment SRV4606 001 3 Mesh Cover SRV4606 125 4 Piezo 14D0503 Y 5 Assembly Wire 00K0632 Y 6 Burner Pan Assembly LP SRV4606 011 Y 7 Media Retainer SRV4606 105 8 Burner Bracket Side Pi...

Страница 46: ...Monessen Glow Getter Owner s Installation Manual 4606 900 Rev A 8 17 46 B Accessories HILOKTN Hi Lo Kit Natural HILOKTP Hi Lo Kit Propane...

Страница 47: ...thirty 30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed MASSACHUSETTS...

Страница 48: ...______________________________________ ________________________________________________________________________________ DO NOT DISCARD THIS MANUAL NOTICE Leave this manual with party responsible for u...

Отзывы: