17
Monessen • Glow Getter Owner’s /Installation Manual • 4606-900 Rev. A • 8/17
The millivolt valve is a self-powered combination gas con
-
trol
THAT DOES NOT REQUIRE 110 VAC TO OPERATE.
F. Connect Optional Wall Switch or
Thermostat (vent free application only)
1. Use 18 awg, two-wire cable, 15 feet maximum length.
2. At one end of the cable, connect both wires to the wall
switch or thermostat. At the other end, connect one
wire to TP/TH and one wire to TH, using fork terminal
or connect the wall switch/thermostat to the two male
(0.25") terminals on the left side of the unit. The color
of the wires does not matter.
Figure 4.3 - Wiring Diagram
NOTE: Log switch wires are not factory connected. Connect log switch wires to the TH/TP and TH valve
terminals as shown.
FP2267
wiring diagram
Log Switch
On/Off Switch
or Optional Wall
Switch, Remote
or T-Stat
ODS Pilot
Millivolt
Valve
TH = 3
TP = 1
TP/TH = 2
ODS
Pilot
CAUTION
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.