Hardware
Device Description Embedded HMI-PLC XV-23x-57
Commissioning
4.2 G
ENERAL NOTES ON CABLING
Cabling should be carried out with special care in order to ensure
interference-free operation.
The EMC values stated in the technical data can only be guaranteed if the
connections and cables are prepared according to the specifications stated.
The cabling must be laid separately from low-voltage cables or isolated with
double or reinforced insulation.
Î
Further information: Installation instructions, General wiring instructions [1]
4.3 C
ONNECTION TO THE POWER SUPPLY
System supply
24 VDC SELV (safety extra low voltage)
Not isolated
Current consumption
Î
Fuse / protection
Internal fuse / protection against reverse polarity
Connector panel
Connected to GND terminal (plastic housing isolated)
Terminal type
Screw terminal (screwdriver No. 3), pluggable
Cross section
min. 0.75 mm
2
/ max. 2.5 mm
2
(lead or wire)
min. AWG24 / max. AWG12
Stripping length
7 mm
Î
Further technical data: chapter 14
+24 VDC GND 0 V
Plug connector: Phönix MSTB 2.5/3-ST-5.08
Phönix Order No. 1757022;
Supplied with unit
(view from the wiring side)
+24 VDC
+24 VDC power supply
GND
Functional ground, connected to connector panel (connection not compulsory)
0 V
Power supply 0V (isolated)
12/05 AWB2776-1581GB
© by Moeller GmbH
11