Operation
2-14
01/00 AWB27-1239-GB
Software addressing
After you have configured the card in the Device
Configurator (see chapter “Software Configuration”),
you can define the inputs using the Sucosoft S40
Editor and scan them with the IL Editor in bit, byte or
word format. The following specifications are
required to address the inputs:
Operand: I
Data type: Bit, Byte, word, double word
1)
Line number: 1 to 9 (0 = Basic unit)
Slot number: 1 to 30
(0 = Basic unit)
Slot number: 0
Word or Byte number
(word: 0 to 34; byte: 0 to 35)
Bit number: 0 to 7
The general syntax rule is:
Operand-data type-line-rack/station-slot/module-byte/word-bit
Example
You wish to scan the inputs of a digital input card.
The card is located in the basic unit (line 0, station 0).
The address 12 was set on the card..
1) A double word access is only possible with adjacent cards.