Engineering
2-4
01/00 AWB27-1239-GB
왘
Use wire diameters of 0.75 mm
2
for the signal
cables.
왘
Lock the plug-in screw terminal in the connector
plug housing and push the cables through the
underside of the housing.
Power supply
The PS416-POW-4x0 power supply card supplies
the cards with 5 V DC from the internal bus of the
rack. The external signal sources must be supplied
separately with 24-V-DC.
The second GND connection is the continuation
of the GND signal.
You can push the cables through the top if neces-
sary. Then, you must push out the plastic window
on the top of the plug housing.