MC-HPG-2x0
Display PLC
Device Description MC-HPG-2x0
Commissioning
Wiring instructions
The stations on the bus system are connected via fieldbus lines complying
with ISO 11898. The cables must accordingly have the following electrical
characteristics:
Parameter Abbreviation Unit Value Value Value Note
min.
nom.
max.
Impedance Z
Ω
108
120
132
Measured between two
signal lines
Specific
resistance
m
Ω
/m
70
For the receiver
module, the differential
voltage on the bus
cable depends on cable
resistance between it
and the sender
Cable delay
ns/m
5
The mininum delay
between to points on
the bus is 0. The
maximum delay is
determined by the bit
timing and the delays of
the sender and receiver
circuits
The figure shows the minimum wiring with shielding between two bus
stations with the Sub-D connector as an example. A bus terminating resistor
(120 Ohm between Pin 2 and Pin 7 of the Sub-D connector) must be
connected at the beginning and the end of each CAN bus. Do not swap
around the two signal wires!
Protective ground
Interface
1
Interface
2
Shield
Protective ground
04/05 AWB2776-1574GB
©
by Moeller GmbH
22
Содержание MC-HPG-2x0 Series
Страница 4: ...II ...
Страница 10: ...MC HPG 2x0 Display PLC Device Description MC HPG 2x0 Introduction 04 05 AWB2776 1574GB by Moeller GmbH 10 ...
Страница 30: ...MC HPG 2x0 Display PLC Device Description MC HPG 2x0 Operation 04 05 AWB2776 1574GB by Moeller GmbH 30 ...
Страница 44: ...MC HPG 2x0 Display PLC Device Description MC HPG 2x0 Disposal 04 05 AWB2776 1574GB by Moeller GmbH 44 ...
Страница 46: ...MC HPG 2x0 Display PLC Device Description MC HPG 2x0 Revision history 04 05 AWB2776 1574GB by Moeller GmbH 46 ...