MC-HPG-2x0
Display PLC
Device Description MC-HPG-2x0
Commissioning
5.6 C
ONNECTING THE PROGRAMMING INTERFACE
The programming is carried out via the standard Ethernet interface (RJ45).
The connection to the programming PC is implemented using a standard
Ethernet cable (1:1) via a hub or directly using a crosslink cable. The cables
are also available as an accessory (
Section 0).
Before the device is connected to the Ethernet network, the IP address of
the device and the programming PC must be set (
Section 6.7).
IP addresses can be obtained from your system or
network administrator. IP addresses must be uniquely
defined in an Ethernet network. The IP address of all
networks and of the programming PC must be in the
same subnetwork (e.g. 192.168.0.xxx).
Connector assignment
RJ45
connector
Pin No.
Signal
Description
1
TXD
2
TXD+
3
RXD+
4 -
5 -
6
RXD
Socket, 8pole
7 -
RJ45
8 -
1
2
3
4
5
6
7
8
Alternatively, programming can also be implemented via the RS232 serial
interface on COM1. This interface is not isolated. The GND connection is
implemented directly on the housing potential (
Section 12).
Cables connected to the programming interface (Ethernet or serial) must be
laid separately from the low-voltage cables.
A detailed description of the project download is
provided in the “XSoft” system description or in the
appropriate software documentation.
04/05 AWB2776-1574GB
©
by Moeller GmbH
20
Содержание MC-HPG-2x0 Series
Страница 4: ...II ...
Страница 10: ...MC HPG 2x0 Display PLC Device Description MC HPG 2x0 Introduction 04 05 AWB2776 1574GB by Moeller GmbH 10 ...
Страница 30: ...MC HPG 2x0 Display PLC Device Description MC HPG 2x0 Operation 04 05 AWB2776 1574GB by Moeller GmbH 30 ...
Страница 44: ...MC HPG 2x0 Display PLC Device Description MC HPG 2x0 Disposal 04 05 AWB2776 1574GB by Moeller GmbH 44 ...
Страница 46: ...MC HPG 2x0 Display PLC Device Description MC HPG 2x0 Revision history 04 05 AWB2776 1574GB by Moeller GmbH 46 ...